Figure 3: Current Sensor Keca 80 C184 / Keca 80 C216 - ABB UniGear Series Engineering Manual

Table of Contents

Advertisement

U NIG E AR DIG ITAL
KECA 80 C184 / KECA 80 C216
For dynamic current measurement (protection purposes) the ABB sensors KECA 80 C184, and
KECA 80 C216, fulfil requirements of protection class 5P up to an impressive value reaching
the rated short-time thermal current I
sensors, measuring class 0.5 is reached for continuous current measurement in the extended
accuracy range from 5 % of the rated primary current I
common for conventional current transformers), but even up to the rated continuous thermal
current I
(1 250 A or 3 150 A). That provides the possibility to designate the corresponding
cth
accuracy class as 5P400, proving excellent linearity and accuracy measurements.

Figure 3: Current sensor KECA 80 C184 / KECA 80 C216

Technical parameters
– Continuous thermal current
– Rated primary current
– Accuracy class
1V LG 5 000 07 E
(31.5 kA). With KECA 80 C184 and KECA 80 C216
th
not only up to 120 % of I
pr
1 250 / 3 150 A
80 A / 150 mV at 50 Hz or 80 A / 180 mV at 60 Hz
0.5 / 5P400