Huawei TP48200A-HX09A2 User Manual page 50

Outdoor power system
Hide thumbs Also See for TP48200A-HX09A2:
Table of Contents

Advertisement

TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual
Maintenance
Item
TCUA control
board
TEC04C
Air filter
Electrical
specifications
Preventive
maintenance
inspection
(PMI)
Appearance
Grounding
Issue 02 (2019-02-26)
Maintenance Task
Check
Check
Whether
Method
The TCUA
By observing,
control board
and checking
works
the indicator
normally.
and alarms.
The TEC04C
By observing,
works
and checking
normally.
the fan and the
temperature.
The air filter is
View the air
covered by
filter.
dust.
The output
Multimeter.
voltage is
normal.
Indicators are
By observing.
normal.
The paint or
By observing.
electroplated
coating on the
cabinet flakes
off or has
scratches.
The ground
By observing
point properly
the grounding
connects to the
and using a
ground bar in
screwdriver or
Copyright © Huawei Technologies Co., Ltd.
4 Maintenance
Repair When
Measures
The TCUA
Replace the
control board
TCUA control
works
board.
abnormally.
The TEC
Replace the
module is
TEC04C.
damaged and
cannot
effectively cool
the air.
Overtemper
Replace the air
ature alarm
filter.
happens
frequently
and the
temperature
inside the
cabinet is
much higher
than the
ambient
temperature.
Dust
accumulates
on the air
filter.
The battery
For details, see
circuit voltage
4.2 Rectifying
or load circuit
Common
voltage exceeds
Faults.
its threshold.
An alarm is
generated.
The surface is
Repaint or
damaged or
repair the shell.
distorted.
The cable
Secure the
connecting the
ground point or
ground point
replace the
and the ground
cable.
43