1.4 Working Principles
Figure 1-5
distribution unit (PDU). The rectifiers convert the AC power input into -48 V DC power
output, which is directed by the DC PDU to DC loads along different routes.
When the AC power is normal, rectifiers power DC loads and charge batteries. When the AC
power is absent, rectifiers stop working and batteries start to power loads. After the AC power
resumes, rectifiers power DC loads and charge batteries again.
The SMU monitors the operating status of each component in the power system in real time
and performs appropriate intelligent control. When detecting a fault, the SMU generates an
alarm. The SMU monitors and regulates the temperature control unit based on the temperature
measured by the temperature sensor to ensure the normal operating temperature for the
cabinet.