Huawei TP48200A-HX09A2 User Manual page 18

Outdoor power system
Hide thumbs Also See for TP48200A-HX09A2:
Table of Contents

Advertisement

TP48200A-HX09A2, TBC300A-TCA2 Outdoor Power
System
User Manual
breaker
Figure 2-4 AC output unit (Multi-purpose socket and RCD)
(1) All-purpose socket
Table 2-1
Table 2-1 AC PDU configurations
Power Grid
Mode
110 V AC
dual-live-wire
Issue 02 (2019-02-26)
(neutral wire)
(2) RCD
describes the AC PDU configurations for the TP48200A-HX09A2.
AC Input
AC Surge
Circuit
Protection
Breaker
Class
One
Class B. The
2-pole 125
normal current
A circuit
(In) is 30 kA,
breaker
and the
maximum
current (Imax) is
60 kA.
Copyright © Huawei Technologies Co., Ltd.
(3) AC load circuit breaker and neutral wire terminal
AC Load
Circuit
Breaker
One
2-pole 10
A circuit
breaker
2 Components
device (SPD)
Maintenance Socket
and Its Protection Mode
Multi-purpose socket and
10 A residual current
device (RCD).
NOTE
110 V AC dual–live wire
input:
There is a neutral wire by
default and the
maintenance output
voltage is 110 V AC. If
you need an output
voltage of 220 V AC,
change the cable
connections to the
maintenance socket based
on
Figure
2-5.
If there is no neutral wire,
change the cable
11