Connection Of Motor With Encoder (Vector Control) - Mitsubishi Electric A800 Plus Instruction Manual

Separated converter type, roll to roll function
Hide thumbs Also See for A800 Plus:
Table of Contents

Advertisement

Connection of motor with encoder (vector control)

2.8
Connection of motor with encoder (vector
control)
Using encoder-equipped motors together with a vector control compatible option enables speed and torque control operations
under orientation control, encoder feedback control, and full-scale vector control.
This section explains wiring for use of the FR-A8AP.
Appearance and parts name of FR-A8AP
Terminal layout
Symbol
Name
a
Mounting hole
b
Terminal block
c
Encoder type selection switch (SW3)
d
CON2 connector
Terminating resistor selection switch
e
(SW1)
Switch for manufacturer setting
f
(SW2)
g
Connector
h
LED for manufacturer check
Terminals of the FR-A8AP
Terminal
symbol
PA1
Encoder A-phase signal input terminal
PA2
Encoder A-phase inverse signal input terminal
PB1
Encoder B-phase signal input terminal
PB2
Encoder B-phase inverse signal input terminal
PZ1
Encoder Z-phase signal input terminal
PZ2
Encoder Z-phase inverse signal input terminal
PG
Encoder power supply (positive side) input terminal
SD
Encoder power supply ground terminal
PIN
Not used.
PO
NOTE
• When the encoder's output voltage differs from its input power supply voltage, the signal loss detection (E.ECT) may occur.
• Incorrect wiring or faulty setting to the encoder will cause a fault such as an overcurrent (E.OC[ ]) and an inverter
overload (E.THT).
Correctly perform the encoder wiring and setting.
60
INSTALLATION AND WIRING
Front view
(a)
(d)
(f)
1
2
PIN and PO
(c)
are not used.
(e)
(a)
Used for installation to the inverter.
Connected with the encoder.
Switches the encoder type (differential line driver/complementary).
Used for extension
Switches ON or OFF the internal terminating resistor.
Do not change from the initially-set status. (Switches 1 and 2 are OFF
Connected to the option connector of the inverter.
Not used.
Terminal name
(a)
(h)
O
N
SW2
SW3
(a)
(b)
Description
A-, B- and Z-phase signals are input from the encoder.
Input terminal for the encoder power supply.
Connect the external power supply (5 V, 12 V, 15 V, 24 V)
and the encoder power cable. When the encoder output is
the differential line driver type, only 5 V can be input. Make
the voltage of the external power supply same as the
encoder output voltage. (Check the encoder specification.)
Rear view
1
2
Description
(a)
(a)
Refer
to page
63
61
61
.) —
O
N
10

Advertisement

Table of Contents
loading

Table of Contents