Peripheral Devices - Mitsubishi Electric A800 Plus Instruction Manual

Separated converter type, roll to roll function
Hide thumbs Also See for A800 Plus:
Table of Contents

Advertisement

Peripheral devices

2.1
Peripheral devices
2.1.1
Inverter and peripheral devices
(c) Three-phase AC power supply
(d) Moulded case
circuit breaker
(MCCB) or earth
leakage current
breaker (ELB),
fuse
(e) Magnetic
contactor
(MC)
(f) AC reactor
(FR-HAL)
(g) Noise filter
(h) High power factor converter
(FR-HC2)
NOTE
• To prevent an electric shock, always earth (ground) the motor, the inverter, and the converter unit.
• Do not install a power factor correction capacitor or surge suppressor or capacitor type filter on the inverter's output side. Doing
so will cause the inverter to trip or the capacitor and surge suppressor to be damaged. If any of the above devices is connected,
immediately remove it. When installing a molded case circuit breaker on the output side of the inverter, contact the manufacturer
of the molded case circuit breaker.
• Electromagnetic wave interference
The input/output (main circuit) of the inverter or the converter unit includes high frequency components, which may interfere
with the communication devices (such as AM radios) used near the inverter or the converter unit. In this case, activating the
EMC filter of the converter unit may minimize interference. (Refer to
• For details of options and peripheral devices, refer to the respective Instruction Manual.
14
INSTALLATION AND WIRING
(b) Converter unit
(FR-CC2)
R/L1 S/L2 T/L3
N/-
P/+
P/+
N/-
Earth
(Ground)
(i) Brake unit
(FR-BU2)
P/+
PR
P/+
PR
(j) Resistor unit
(MT-BR5)
: Install these options as required.
(a) Inverter
(FR-A802)
P/+
N/-
Earth
U V W
(Ground)
(m) Induction
motor
Earth
(Ground)
page
78.)
(k) USB connector
USB host
(A connector)
Communication
status indicator
(LED)(USB host)
USB device
(Mini B connector)
Personal computer
(FR Configurator 2)
(l) Noise filter
USB

Advertisement

Table of Contents
loading