7 - Measuring Pro protections

Availability (Performance)

The following is a complete list of the protections (and related parameters) available with all the trip units of the Touch range equipped with an Ekip
Measuring Pro module, in the Protections and Advanced menus:
Name
UV
OV
VU
(1)
UF
(2)
OF
(2)
RP
Phase Sequence
Cosφ
(1)
Protection not active if the highest of the voltages measured is in any case less than 30% of Un.
(2)
Protection not active for voltages <30V.
(3)
Detailed description in the Design Engineer's manual
(4)
Locking Function available via Ekip Connect.

Summary table of Measuring Pro protections

ANSI
ABB
Threshold
(3)
U8 = 0,05....0,98 Un
UV
27
step = 0.001 Un
U9 = 1....1,5 Un
OV
59
step = 0.001 Un
U14 = 2...90 %
VU
47
step = 1 %
f12 = 0,9....1 fn
UF
81L
step = 0.001 fn
f13 = 1....1,1 fn
OF
81H
step = 0.001 fn
P11 = -1...-0.05 Sn
RP
32R
step = 0.001 Sn
Ulive = 0.5...1.1 Un; step = 0.001 Un
∆U = 0.02...0.12 Un; step = 0.001 Un
Synchro-
∆f = 0.1...1 Hz; step = 0.1 Hz
25
check
∆Cos φ = 5...50° elt; step = 5° elt
tsyn = 0.1...3 s; step = 0.1 s
Cyclic
direction of
47
1-2-3 or 3-2-1
the phases
Cos φ = 0.5...0.95
Cos φ
78
step = 0.01
(1)
Calculation of t
is valid for values exceeding the tripping threshold of the protection.
t
(2)
Valid tolerances with steady-state energized trip unit or trip unit energized by auxiliary power supply, tripping time ≥ 100 ms, temperature and
currents within operating limits. If these conditions are not guaranteed, the tripping time tolerance of ± 10 % will become ± 20%.
(3)
ANSI / IEEE C37-2 encoding.
(4)
Valid tolerance for frequencies in the range: fn ± 2 %. For frequency outside the range a tolerance of ± 5 % applies.
15 | © 2018 ABB | 1SDH001316R0002 - ECN000086018 - Rev. C
Protection against
Minimum voltage
Maximum voltage
Voltage unbalance
Minimum frequency
Maximum frequency
Reverse active power
Phase sequence error
Power factor error
Threshold
Time
X
X
X
X
X
X
X
X
X
X
X
X
X
--
X
--
Tolerance
Time
threshold
t8 = 0.05...120 s
± 2 %
step = 0.01 s
t9 = 0.05...120 s
± 2 %
step = 0.01 s
t14 = 0.5...60 s
± 5 %
step = 0.5 s
t12 = 0,06...300 s
± 1 %
(4)
step = 0.01 s
t13 = 0,06...300 s
± 1 %
(4)
step = 0.01 s
t11 = 0.5...100 s
± 10 %
step = 0.1 s
tref = 0.1...30 s
± 10 %
step = 1 ms
-
-
-
-
Auxiliary functions
(3) (4)
Trip Enable, Lock
Trip Enable, Lock
Trip Enable, Lock
Trip Enable, Lock
Trip Enable, Lock
Trip Enable, Lock
Calculation
Tolerance t
formula t
(1)
t
t
The better of the two values:
± 10 % or ± 40 ms (for a time
t
= t8
set < 5 s) / ± 100 ms (for a
t
time set ≥ 5 s)
The better of the two values:
± 10 % or ± 40 ms (for a time
t
= t9
set < 5 s) / ± 100 ms (for a
t
time set ≥ 5 s)
The better of the two values:
± 10 % or ± 40 ms (for a time
t
= t14
set < 5 s) / ± 100 ms (for a
t
time set ≥ 5 s)
The better of the two values:
± 10 % or ± 40 ms (for a time
t
= t12
set < 5 s) / ± 100 ms (for a
t
time set ≥ 5 s)
The better of the two values:
± 10 % or ± 40 ms (for a time
t
= t13
set < 5 s) / ± 100 ms (for a
t
time set ≥ 5 s)
The better of the two values:
± 10 % or ± 40 ms (for a time
t
= t11
set < 5 s) / ± 100 ms (for a
t
time set ≥ 5 s)
-
-
-
-
-
-
Ekip Touch protection trip unit | 7 - Measuring Pro protections