5-2-3. Control details for blocks of indoor units
Follow the instructions below to make the Peak Cut control settings for each control level for given blocks of
indoor units.
If the block settings have not been made, refer to section 4-5 for how to make the block settings.
Control level
Batch Operations
Click to make settings for
all blocks at once.
(1) Scroll up or down to display the block whose settings are to be made. To make settings for all blocks at
once, check the [Batch Operations] checkbox.
Then, select the control method for each control level, referring to the table below.
Note: Only the control method "OFF" is effective for Air To Water (PWFY) units. Other methods can be selected, but are not
effective.
Control Method
None
Peak Cut control will not be performed.
During the Peak Cut control, the set temperature in the Cool or Dry mode will be offset by +2ºC (+4ºF),
and the set temperature in the Heat mode will be offset by -2ºC (-4ºF).
±2ºC (±4ºF)
During the Peak Cut control, free-plan indoor units and A-control Mr. Slim indoor units (M-Series/
P-Series indoor units) will go in to the Thermo-OFF state, and the units older than free-plan units will
Fan
*1
operate in the Fan mode. (When the units are in the Thermo-OFF state, the operation mode on the
remote controller LCD will not change.)
During the Peak Cut control, the units will stop.
*1
OFF
*1 When the indoor unit Peak Cut control function is used during the heating operation, it takes a while to resume operation to prevent cold
air draft. This may negatively affect the performance of the unit for a certain period of time after the operation is resumed. To ensure
maximum performance, it is recommended to use an outdoor unit capacity-save control function (that will not stop the compressor
operation) during the heating operation. If the indoor unit Peak Cut control function is still used, selecting [3] minutes in the Control Time
section is recommended.
WT07138X02
Table 5-3 Indoor Unit Control Method
Note:
Peak Cut
control will not be performed during the Fan or Auto mode.
Note: When the unit of temperature is Fahrenheit, the set temperature may not be offset by ±4ºF
exactly because 2ºC is used for the calculation first, and then the temperature in Celsius is
converted into the temperature in Fahrenheit.
Note: The set temperature will be adjusted within the set temperature restrictions settings.
Refer to section 6-1 for details.
Note: If the control method is set to [OFF] and the Control Time is set to [30] minutes, the groups that
are operated in the Peak Cut control cannot be operated from any controller.