LED
Color
Fail-safe inputs / double inputs
F_DI z
LED
LED
(input x,
x
x+1
(x+1)+,
Red
(x+1)-)
Red
LED
LED
x
Green
Green
Green
Green
Inputs x+1 (DI 1+, 3+, .. 19+) can be set individually via parameter p10040 (TM54F).
1)
p10040 (TM54F) = 0: Input x+1 is an NC contact.
p10040 (TM54F) = 1: Input x+1 is NO contact.
Factory setting: p10040 (TM54F) = 0 for all inputs x+1.
Single digital inputs, not fail-safe
DI x
Green
Fail-safe digital outputs with associated readback channel
F_DO y
Green
(0+..3+,
0-..3-)
Readback input DI 2y for output F_DO y (y = 0..3) at test stop.
The status of the LEDs also depends on the type of external circuit.
DI 2y
Green
Commissioning Manual
Commissioning Manual, (IH1), 01/2011, 6SL3097-4AF00-0BP1
Status
NC contact / NC contact
Continuou
Different signal states at input x and x+1
s light
No signal at input x and no signal at input x+1
NC contact / NO contact
Same signal states at input x and x+1
Continuou
No signal at input x and a signal at input x+1
s light
x+1
NC contact / NC contact
Continuou
A signal at input x and a signal at input x+1
s light
NC contact / NO contact
A signal at input x and no signal at input x+1
Continuou
s light
Off
No signal at digital input x (x = 20..23)
Continuou
Signal at digital input x
s light
Continuou
Output y (y=0 .. 3) carries a signal
s light
Off
One of the two output lines y+ or y- or both lines of output y
carry a signal
Continuou
Both output lines y+ and y- carry no signal
s light
Description, cause
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
: (z = 0..9, x = 0, 2, ..18)
1)
Diagnostics
3.1 Diagnostics via LEDs
Remedy
203