7.
Insert the communication module in the appropriate slot (Figure 2). The
communication module pushes the port cover downward when inserted.
4.4
Wiring I/O ports
Wire the RMC I/O ports to monitor, control and power external devices. Wiring for
power is required if there is no external supply powering the device.
To wire the I/O port:
IMPORTANT NOTE: Refer to the RMC user drawings for I/O wiring
details for specific external devices. See the Additional information
section.
CAUTION – Equipment damage. An external device can be powered
from pin 1 (PWR) on any of the AIs (Table 3) or the AO (Table 4). The
output voltage at the PWR pin is dependent upon the external power
supply connected to the CHARGER/EXT PWR port.
Before connecting to these pins, ensure that the external device is
compatible with the input voltage at the CHARGER/EXT PWR port.
Connecting an incompatible device may result in damage to the device.
1.
Use a slotted screwdriver to pry the terminal connector off the electronic board.
2.
Trim the wire covering back ¼ inch on each wire.
3.
Loosen the terminal connector screws for the correct pin according to the I/O
tables. See sub-sections 4.4.1, 4.4.2, 4.4.3, and 4.4.4 in this guide.
4.
Insert the wires in the required pins. If powering the device from the AI or the
AO:
a.
Use pin 1 (PWR) and pin 3 (GND) for devices attached to the AI.
b.
Use pin 1 (PWR) and pin 4 (GND) for devices attached to the AO.
5.
Tighten the terminal connector screws.
NOTICE – Property damage. Do not overtighten the terminal
connector screws as this may damage the wire.
6.
Insert the terminal connector back on the I/O port if it was removed.
BAT CHARGER/EXT PWR
PI
Figure 2: COMM terminals and modules
1
2
3
4
5 6
7 8
9
1
2
COMM 1
COMM 1
3
4
5 6
7 8
9
COMM 2
RMCIO
EXPANSION
COMM 2