Configuring Communications - ABB RMC-100 Startup Manual

Remote modular controller
Hide thumbs Also See for RMC-100:
Table of Contents

Advertisement

6.4
Changing the LCD display
The factory configuration has a default date and time display. To change the display
to preferred settings:
1.
On the Station Setup tab, scroll down to the LCD Display Date/Time Format
section (Figure 16).
2.
Select the preferred Date/Time Format (mmddyy or yymmdd).
3.
Select the preferred Date Separator (slash, dash, or period).
4.
Select the preferred Time Separator (colon or period).
5.
Click Send to save all of the station settings.

7 Configuring communications

7.1
Configuring the COMM ports
The configuration is for COMM1 and COMM 2 communication ports when
connecting one or more serial devices. These ports are software configurable to
support RS-232, RS-422, and RS-485. To configure the ports:
1.
Ensure the power LED on the COMM module is on (green).
2.
In PCCU, click Communications on the navigation tree. The Communications
Setup tab displays (Figure 17).
Figure 16: LCD display date and time format
Figure 17: COMM port configuration
2105551-001 rev. AC | 23