Safety Integrated basic functions
9.1 General information
● When Safety Integrated is commissioned for the first time, the following applies:
● In the case of a series commissioning of Safety or in the case of spare part installation,
● Change password for the drives
● Change password for the TM54F
If you need to change safety parameters but you do not know the safety password, proceed
as follows:
1. Set the entire drive unit (Control Unit with all connected drives/components) to the factory
2. Recommission the drive unit and drives.
3. Recommission Safety Integrated.
Or contact your regional Siemens office and ask for the password to be deleted (complete
drive project must be made available).
Overview of important parameters for "Password" (see SINAMICS S120/S150 List Manual)
● p9761 SI password input
● p9762 SI password new
● p9763 SI password acknowledgement
● p10061 SI password input TM54F
● p10062 SI password new TM54F
● p10063 SI password acknowledgement TM54F
364
– Safety passwords = 0
– Default setting for p10061 = 0
– Default setting for p9761 = 0
In other words:
The safety password does not need to be set during first commissioning.
the following applies:
– The safety password is retained on the memory card and in the STARTER project.
– No safety password is required in the case of spare part installation.
– p0010 = 95 Commissioning mode
– p9761 = Enter "old safety password".
– p9762 = Enter "new password".
– p9763 = Confirm "new password".
– The new and confirmed safety password is valid immediately.
– p0010 = 95 Commissioning mode
– p10061 = Enter "Old TM54F Safety Password" (factory setting "0")
– p10062 = Enter "new password"
– p10063 = Acknowledge "new password"
– The new and acknowledged safety password is valid immediately.
setting.
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5