1MRK 500 127-UEN D
Section 7
7.1
Monitoring
7.1.1
Indications
The operation of the IED can be monitored via three different indications on the LHMI.
•
Three indicator LEDs with fixed functionality: Ready, Start and Trip
•
15 programmable three-color alarm LEDs which can present 45 virtual LED states
•
•
An auto-indicating message on the display.
7.1.1.1
Using auto-indication messages
Auto-indication messages are shown in a dialog box that is displayed when the disturbance
recorder is triggered. The indication dialog box shows a list of current disturbance recordings
one by one. To scroll the dialog, use
1.
Read the auto-indication message in the dialog box.
The message contains the same information that is available for disturbance recordings.
2.
Press
3.
Press
the Clear view and to clear messages.
670 series
Operation manual
Operating procedures
For each on state LED color and for the LED off state, texts can be programmed with
PCM600 and via LHMI. These texts are displayed on the LHMI.
To activate the auto-indication message function, the disturbance recorder
function has to be activated and properly configured. Check also that the
setting Main menu/Configuration/HMI/Screen/SCREEN:1/AutoIndicationDRP
On .
is set to
to see more detailed information.
to close the auto-indication message without clearing it or press
and
.
Section 7
Operating procedures
GUID-E3CC6AB4-D6C4-4504-A0F2-CA76EA3D7FCD v10
AMU0600430 v9
to activate
51