Mitsubishi Electric A960GOT User Manual page 55

Human machine interface, graphical operator terminal
Table of Contents

Advertisement

6 HANDLING
6 - 8
(2) Grounding the ground cable
Manufacture the cable used with the GOT with the following method.
When manufacturing the cable, a ferrite core, cable clamp and cable shielding
material are required.
The cable clamp used by Mitsubishi Electric for the EMC specification
compatibility test is shown below.
• TDK brand ZCAT3035-1330 Ferrite Core
• TDK brand ZCAT2436-1330 Ferrite Core
• Mitsubishi Electric Model AD75CK cable clamp
• Japan Zipper Tubing Co., Ltd. Zipper tube SHNJ type
a) BUS connection cable
1) For A8GT-C100/200/300EXSS, A8GT-C100/200/300BS.
• Cut the connection wire protruding from both ends of the cable to the
lengths shown below.
• Peel the sheath (with the length shown below) at both ends of the
cable, and expose the shield braided wire for grounding.
Ferrite Core
GOT side
(ZCAT3035-1330)
Ground wires
130
(280mm
(5.12)
(11.0inch))
Within 360
40
(14.17)
(1.57)
2) For other cables between GOT and base unit
• Wind cable shield material around the cable, and pull out the
grounding braided wire of the cable shield material with the length
shown below.
• Pass the grounding braided wire on the programmable logic controller
side through the core.
GOT side
(ZCAT3035-1330)
Cable shield material
130
Grounding braided
(5.12)
wire(50mm(1.97inch))
Within 150
(5.90)
PLC/GOT side
40
Within 360
(1.57)
(14.17)
Ferrite Core
Within 150
Grounding braided
wire(200mm(7.87inch))
MELSEC-GOT
130
(5.12)
Unit : mm (inch)
PLC side
130
(5.12)
Unit : mm (inch)
(5.90)
6 - 8