Location
Component
LAN switch (optional) UT-H605 or ES1000
Smart array
Fitting bag
controller
for optical
ring
switching
MCB
Box-type
Three-
transformer
phase
power
switch
Recommended Model or
Specifications
Low-
speed
FTLF1323P1BTR-HW
optical
module
PLCLC5S-ST3P302-HW, LC-
Optical
LC-S2-L2,
jumper
3ECA1031LCLC002-01-F, or
LP-LP-2S-P-SM-002
Rated current: 32 A, number of
poles: 2
When the rated AC voltage
on the low-voltage side of
the box-type transformer is
less than or equal to 500 V,
the rated voltage should be
greater than or equal to 500
V. When the rated AC
voltage on the low-voltage
Knife
side of the box-type
fuse
transformer is greater than
switch
500 V and less than or
(solution
equal to 800 V, the rated
1)
voltage should be greater
than or equal to 800 V.
Rated current of the fuse:
32 A; rated current of the
knife fuse switch box ≥ 32 A;
number of poles: 3 (3 fuses
for each knife fuse switch
box)
When the rated AC voltage
on the low-voltage side of
the box-type transformer is
less than or equal to 500 V,
the rated voltage should be
greater than or equal to 500
V. When the rated AC
voltage on the low-voltage
MCCB
side of the box-type
(solution
transformer is greater than
2)
500 V and less than or
equal to 800 V, the rated
voltage should be greater
than or equal to 800 V.
Let-through energy ≤ 1.26 x
6
2
10
A
s
Rated current: 32 A;
number of poles: 3
Component
Source
Can be
purchased
from Huawei
Can be
purchased
from Huawei
Prepared by
the customer
Prepared by
the customer
Prepared by
the customer
6
Quantity
1
2
8
1
Scenario with a
double-column
transformer: 1
Scenario with a
dual-split
transformer: 2