Huawei SmartLogger2000 series Quick Manual page 4

Hide thumbs Also See for SmartLogger2000 series:
Table of Contents

Advertisement

SmartLogger2000-10/10-B/11-B
No.
Port (Silk Screen)
1
RF1, RF2
2
12V OUT
3
12V IN
4
USB
5
SFP1, SFP2
6
ETH1, ETH2
7
DO
8
COM1–COM6
9
Default
10
AC1, AC2
11
12
AI1–AI8
13
AO1–AO6
14
DI1–DI8
Note a: Passive means that the AI port can connect to a sensor that needs to be energized separately.
Note b: Active means that the AI port can connect to a sensor that need not be energized separately.
Function
Reserved
12 V DC output
12 V DC input
USB port
Ethernet optical port
Ethernet electrical
port
Digital output (DO)
RS485
communications
Default key
AC power cable
ports
Shell ground point
Analog input
Analog output (AO)
Digital input (DI)
Description
Reserved.
Provides 12 V DC power supply with a maximum
current of 100 mA.
Connects to the power adapter.
Connects a USB flash drive.
Connects to an ATB or another cascaded
SmartLogger.
Connects to an Ethernet LAN switch, router, POE or
PC device.
Relay output supports 12 V voltage and 0.5 A current.
Six RS485 ports that can be connected to devices
such as the SUN2000, box-type transformer, power
meter, or EMI.
Resets and restarts the Bluetooth module or resets
the SmartLogger IP address to the default IP address
(valid within 5 minutes). The default IP address is
192.168.0.10.
SmartLogger2000-10/10-B: Connects to the A/B/C
three-phase input, and used for PLC with the
SUN2000 over AC power cables.
SmartLogger2000-11-B: disabled
N/A
SmartLogger2000-10: AI1–AI4: 4–20 mA and 0–20
mA input current (passive
0–20 mA input current (active
SmartLogger2000-10-B/11-B: AI1: 0–10 V input
voltage (passive); AI2–AI4: 4–20 mA and 0–20 mA
input current (passive); AI5–AI8: 4–20 mA and 0–
20 mA input current (active)
4–20 mA and 0–20 mA output current
Connects to a dry contact input. GND1 and GND2
are ground ports for DI signals.
3
a
); AI5–AI8: 4–20 mA and
b
)

Advertisement