ABB Busch-priOn Series Technical Reference Manual

Knx technical reference manual

Advertisement

0073-1-7388 │ Rev. 03 │ 01.2011
KNX Technical Reference Manual
Busch-priOn
Pos: 2 /Produkthandbuch - DIN-A4/Titelblätter/Titelblatt - Busch-priOn @ 9\mod_1269242014078_15.doc @ 52250 @
Busch-priOn
innovative and intuitive
Improved control elements. For example, the new 8.9 cm
(3.5") TFT display as informative component of a flush-type
combination is both stylish and efficient. Its menu can be
individually adapted to every building and at all times
provides an overview of the electrical consumers. From here
the heating can be controlled, the lights dimmed or
comprehensive scenes called up that trigger numerous
preprogrammed actions. Meaningful symbols lead even the
untrained user to his objective in just a few steps. The
division of functions into individual areas such as light,
heating or blinds, assists everyone to find his way around
intuitively. Yet, this is not the end of possibilities for the
Busch-priOn® in classical building technology. The display
can also be used for controlling music.
=== Ende der Liste für Textmarke Cover ===
®
®
The combination of pushbutton/rotary control element and
display has a universal operating concept. The definition of
a primary function makes its use particularly easy. The
primary function appears when one approaches the display
(a special proximity sensor is available) or when pressing
the rotary control element. In principle, any switching,
dimming, blinds, scene or sequence function that has been
stored in the unit can be defined as primary function. It is
only when the menu button is pressed that the display
changes to the circuit menu. Up to 8 entries can be
displayed via one symbol. By turning the pushbutton/rotary
control element the user can bring the desired function into
the foreground. An associated text below the focused
symbol is shown (e.g. system settings, room control office,
room control, living room, etc.). By activating the
pushbutton/rotary control element the display changes to the
respective list menu, which can consist of up to 15 different
functions. The user can scroll through these functions by
turning the pushbutton/rotary control element. The function
is selected by pressing the button.

Advertisement

Table of Contents
loading

Summary of Contents for ABB Busch-priOn Series

  • Page 1 0073-1-7388 │ Rev. 03 │ 01.2011 KNX Technical Reference Manual ® Busch-priOn Pos: 2 /Produkthandbuch - DIN-A4/Titelblätter/Titelblatt - Busch-priOn @ 9\mod_1269242014078_15.doc @ 52250 @ ® Busch-priOn innovative and intuitive The combination of pushbutton/rotary control element and display has a universal operating concept. The definition of Improved control elements.
  • Page 2: Safety Instructions

    KNX Technical Reference Manual ® Busch-priOn Pos: 4.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/S - Z/Sicherheitshinweise @ 9\mod_1269243781484_15.doc @ 52309 @ 1 Safety instructions Pos: 4.2 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Wechsel von ein- auf zweispaltig ++++++++++++ @ 9\mod_1268898451593_0.doc @ 52140 @ Pos: 4.3 /Produkthandbuch - DIN-A4/Busch-priOn/Sicherheitshinweise/Sicherheitshinweise @ 9\mod_1269245364203_15.doc @ 52365 @ Pos: 4.4 /Produkthandbuch - DIN-A4/Busch-priOn/Sicherheitshinweise/Haftungsausschluss @ 16\mod_1292413036321_15.doc @ 97864 @ Work on the 230 V power supply system must Disclaimer...
  • Page 3 os: 4.6 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++Wechsel zwei- auf einspaltig ++++++++++++ @ 9\mod_1268898591406_0.doc @ 52144 @ Pos: 6.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/M - R/Maßzeichnungen @ 9\mod_1269243888140_15.doc @ 52313 @ 1 Dimensional drawings Pos: 6.2 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Wechsel von ein- auf zweispaltig ++++++++++++ @ 9\mod_1268898451593_0.doc @ 52140 @ Pos: 6.3 /Produkthandbuch - DIN-A4/Busch-priOn/Maßzeichnungen/Maßzeichnungen_Best_Nr_ABB @ 15\mod_1289220462033_15.doc @ 96904 @ Support frame for Busch-priOn®...
  • Page 4 KNX Technical Reference Manual ® Busch-priOn Pos: 8.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/M - R/Rahmenlose Vielfalt @ 9\mod_1269243889687_15.doc @ 52318 @ 1 Frame-free variety Pos: 8.2 /Produkthandbuch - DIN-A4/Busch-priOn/Rahmenlose Vielfalt/Rahmenlose Vielfalt @ 9\mod_1269245480843_15.doc @ 52373 @ ® It is not merely individuality which characterises Busch-priOn during programming of the individual buttons: ®...
  • Page 5 Pos: 10.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/G - L/Kombinationen nach Wunsch @ 9\mod_1269243898187_15.doc @ 52323 @ 1 Combinations as desired Pos: 10.2 /Produkthandbuch - DIN-A4/Busch-priOn/Kombinationen nach Wunsch/Kombinationen nach Wunsch_Best_Nr_ABB @ 11\mod_1279629873579_15.doc @ 84942 @ ® The control elements and end strips can be freely combined for Busch-priOn with regard to colour and function.
  • Page 6: Table Of Contents

    KNX Technical Reference Manual ® Busch-priOn Pos: 12.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/G - L/Kein gewöhnliches KNX-Bedienelement @ 9\mod_1269243899796_15.doc @ 52328 @ 1 Not just any KNX control element Pos: 12.2 /Produkthandbuch - DIN-A4/Busch-priOn/Kein gewöhnliches KNX-Bedienelement/Kein gewöhnliches KNX-Bedienelement - Text @ 9\mod_1269426042218_15.doc @ 52740 @ Each of the buttons of the Busch-priOn®...
  • Page 7 Pos: 12.5 /Produkthandbuch - DIN-A4/Busch-priOn/Kein gewöhnliches KNX-Bedienelement/Kein gewöhnliches KNX-Bedienelement - Tabelle - Allg. Funktionen @ 15\mod_1289904254518_15.doc @ 97280 @ General functions Function Large-area control Rotary control 8,9 cm (3,5") TFT display Movement Page number element element with control element detector Delay ●...
  • Page 8 KNX Technical Reference Manual ® Busch-priOn Pos: 14.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/A - F/Der richtige Ankoppler @ 9\mod_1269243900921_15.doc @ 52333 @ 1 The right bus coupler Pos: 14.2 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Wechsel von ein- auf zweispaltig ++++++++++++ @ 9\mod_1268898451593_0.doc @ 52140 @ Pos: 14.3 /Produkthandbuch - DIN-A4/Busch-priOn/Der richtige Ankoppler/Der richtige Ankoppler - Tabelle+Text_Best_Nr_ABB @ 16\mod_1291294382201_15.doc @ 97635 @ Only one bus coupler is mounted behind every Busch- Maximum number of Busch-priOn®...
  • Page 9 Pos: 16.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/A - F/Einfache Montage @ 9\mod_1269243901843_15.doc @ 52338 @ 1 Easy to mount Pos: 16.2 /Produkthandbuch - DIN-A4/Busch-priOn/Einfache Montage/Einfache Montage - Text @ 10\mod_1272614580478_15.doc @ 53803 @ The carrier frame serves to hold and make contact with the individual control elements, the 8.9 cm (3,5”) TFT display, the end strips and the flush-type bus coupler.
  • Page 10 KNX Technical Reference Manual ® Busch-priOn Pos: 18.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/M - R/Raumtemperaturregler @ 13\mod_1286268674432_15.doc @ 91479 @ 11 Room thermostat Pos: 18.2 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/P - R/Raumtemperaturregler-Display @ 13\mod_1286269387786_15.doc @ 91504 @ 2 Room thermostat with display Pos: 18.3 /Produkthandbuch - DIN-A4/Überschriften/3.
  • Page 11 Pos: 18.12 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/A - F/Betriebsarten @ 13\mod_1286276050737_15.doc @ 91535 @ 22 Operating modes Pos: 18.13 /Spezial/Neues Layout 2010/Steuermodule_Neues_Layout_2010/++++++++++++ Wechsel von ein- auf zweispaltig ++++++++++++ @ 9\mod_1268898451593_0.doc @ 52140 @ Pos: 18.14 /Produkthandbuch - DIN-A4/Busch-triton/Raumtemperaturregler/Betriebsarten_zwei @ 13\mod_1286273939022_15.doc @ 91528 @ 2 Night setback: The temperature can be Standby: Standby mode lowers the reduced during the night.
  • Page 12 KNX Technical Reference Manual ® Busch-priOn Pos: 20.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/M - R/Planerunterstützung RTR @ 13\mod_1286265494848_15.doc @ 91464 @ 1 Planner support for RTC Pos: 20.2 /Produkthandbuch - DIN-A4/Busch-triton/Bedienung/Betriebsarten @ 13\mod_1284551640044_15.doc @ 89965 @ 2 Operating modes The room thermostat has four operating modes: •...
  • Page 13 Internal temperature sensor The device has an integrated temperature sensor. The measured value enters the control as actual value. The value can also be shown on the display. In addition, the measured temperature can be transferred to the bus via the 2-byte communication object "Send actual value - temperature sensor", to be shown on the display, for example.
  • Page 14 KNX Technical Reference Manual ® Busch-priOn Pos: 20.11 /Produkthandbuch - DIN-A4/Busch-triton/Bedienung/Regler @ 13\mod_1284636897353_15.doc @ 90034 @ 2222 Controller The room thermostat can be used exclusively for heating, exclusively for cooling or for heating and cooling. If the room thermostat is to heat or cool, the switchover from heating to cooling or cooling to heating can occur automatically by means of the room thermostat.
  • Page 15 Pos: 20.14 /Produkthandbuch - DIN-A4/Busch-triton/Bedienung/Stetigregler @ 13\mod_1284706827607_15.doc @ 90054 @ 33 Continuous controller A continuous controller has a continuously changing control value which can accept values between 0 and 100%. For the KNX this control value signal is converted to a 1-byte value, which means that control value 0% corresponds to value "0" and control value 100% to value "255".
  • Page 16 KNX Technical Reference Manual ® Busch-priOn Pos: 20.18 /Produkthandbuch - DIN-A4/Busch-triton/Bedienung/Regelparameter @ 13\mod_1284716229894_15.doc @ 90078 @ 3223 Control parameter for PWM controller and continuous controller (Fan coil) For continuous control behaviour and for a switching PWM controller, the preset control parameters can be used via the installation type of the heating or cooling system.
  • Page 17 "Setpoint heating" is the default setting. In regions where the cooling function is more important, it is recommended that you change this parameter to "Setpoint cooling". This makes it easier to set the room thermostat and raise the cooling setpoint (standby temperature cooling and night setback cooling).
  • Page 18 KNX Technical Reference Manual ® Busch-priOn Pos: 20.25 /Produkthandbuch - DIN-A4/Busch-triton/Bedienung/Fan Coil Allgemein @ 13\mod_1284722830008_15.doc @ 90126 @ 33 Fan coil, general The ventilation convectors, also called fan convectors or fan coil units, are used for decentralized heating and cooling. They are installed in the room and supplied via a central heating and cooling system.
  • Page 19 Pos: 20.28 /Produkthandbuch - DIN-A4/Busch-triton/Bedienung/Sommerkompensation @ 13\mod_1284723143680_15.doc @ 90142 @ 2222 Summer compensation To save energy and to maintain a reasonable temperature difference when entering an air-conditioned building, the room temperature should be adjusted in relation to the external temperature (summer compensation according to DIN 1946). The room temperature is raised by adjusting the "Cooling setpoint comfort mode".
  • Page 20 KNX Technical Reference Manual ® Busch-priOn Pos: 20.30 /Produkthandbuch - DIN-A4/Busch-triton/Bedienung/Winterkompensation @ 13\mod_1284723385008_15.doc @ 90150 @ 3 Winter compensation To improve comfort and to keep the temperature difference when entering a room with large window areas in comfortable limits, an increase of the room temperature, as a function of the outside temperature, should be performed during the winter (winter compensation).
  • Page 21: Switching, Rocker Total

    Pos: 22.1 /Produkthandbuch - DIN-A4/Überschriften/1. Ebene/A - F/Applikationsbeschreibungen @ 9\mod_1269243903093_15.doc @ 52343 @ 1 Description of application Pos: 22.2 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Schalten, Wippe Gesamt @ 9\mod_1269245200625_15.doc @ 52356 @ 22 Switching, rocker total Pos: 22.3 /KNX/Applikationsbeschreibungen/Applikationen - App/Schalten_Wippe_gesamt/App. - Schalten, Wippe Gesamt - DIN-A4 @ 9\mod_1269244387750_15.doc @ 52348 @ With the "Switch, rocker total"...
  • Page 22: Dimming, Rocker Left/Right

    KNX Technical Reference Manual ® Busch-priOn Pos: 22.9 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/A - F/Dimmen, Wippe Links / Rechts @ 9\mod_1269423462609_15.doc @ 52694 @ 2 Dimming, rocker left/right Pos: 22.10 /KNX/Applikationsbeschreibungen/Applikationen - App/Dimmen_Wippe_links_rechts/App. - Dimmen, Wippe links / rechts - DIN-A4 @ 9\mod_1269423217171_15.doc @ 52689 @ 2 With the "Dimming, rocker left/right"...
  • Page 23: Value Sender, Rocker Total

    Pos: 22.16 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/U - Z/Wertsender, Wippe Gesamt @ 9\mod_1269425035171_15.doc @ 52725 @ 22 Value sender, rocker total Pos: 22.17 /KNX/Applikationsbeschreibungen/Applikationen - App/Wert Wippe/App. - Wertsender, Wippe Gesamt - DIN-A4 @ 9\mod_1269424602000_15.doc @ 52720 @ With the "Value sender, rocker total" application, a telegram with the predefined value is sent out at an actuation of the right or left side of the rocker.
  • Page 24: Value Sender, 2 Objects, Rocker Left/Right

    KNX Technical Reference Manual ® Busch-priOn Pos: 22.21 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/U - Z/Wertsender, 2 Objekte, Wippe Links / Rechts @ 9\mod_1269431015140_15.doc @ 52763 @ 22 Value sender, 2 objects, rocker left/right Pos: 22.22 /KNX/Applikationsbeschreibungen/Applikationen - App/Wertsender_2_Objekte_Wippe_links_rechts/App. - Wertsender, 2 Objekte, Wippe Links / Rechts - DIN-A4 @ 9\mod_1269428977390_15.doc @ 52758 @ With the "Value sender, 2 objects, rocker left/right"...
  • Page 25: Light Scene Extension Unit With Memory

    Pos: 22.26 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Lichtszenennebenstelle mit Speicherfunktion @ 9\mod_1269436310937_15.doc @ 52783 @ 2 Light scene extension unit with memory function Pos: 22.27 /KNX/Applikationsbeschreibungen/Applikationen - App/Lichtszenennebenstelle_mit_Speicherfunktion/App. - Lichtszenennebenstelle mit Speicherfunktion - DIN-A4 @ 9\mod_1269435757171_15.doc @ 52778 @ Via the application "Light scene extension unit with memory function", a predefined light scene number is called up when the rocker is actuated.
  • Page 26 KNX Technical Reference Manual ® Busch-priOn Pos: 22.31 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Stufenschalter, Wippe Links / Rechts @ 9\mod_1269437464625_15.doc @ 52803 @ 2 Step switch, rocker left/right Pos: 22.32 /KNX/Applikationsbeschreibungen/Applikationen - App/Stufenschalter_Wippe_links_rechts/App. - Stufenschalter, Wippe Links / Rechts - DIN-A4 @ 9\mod_1269437349390_15.doc @ 52798 @ The application "Step switch, rocker left/right"...
  • Page 27 Multiple operation objects, rocker left/right, continued Object name Data type Flags Switching 2, multiple operation (1 Bit) 1 Bit EIS1 / DPT 1.001 C, W, T Switching 2, multiple operation (1 Byte 0..100 %) 1 Byte EIS6 / DPT 5.001 C, W, T Switching 2, multiple operation (1 Byte 0..255) 1 Byte EIS14 / DPT 5.010...
  • Page 28: Short/Long Operation, Rocker Left/Right

    KNX Technical Reference Manual ® Busch-priOn Pos: 22.36 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Kurz-Lang-Bedienung, Wippe Links / Rechts @ 9\mod_1269440952703_15.doc @ 52823 @ 22 Short/long operation, rocker left/right Pos: 22.37 /KNX/Applikationsbeschreibungen/Applikationen - App/Kurz_lang_Bedienung_Wippe_links_rechts/App. - Kurz-Lang-Bedienung, Wippe Links / Rechts - DIN-A4 @ 9\mod_1269440785765_15.doc @ 52818 @ 2 Via the application "Short/long operation, rocker left/right", different values can be sent out with a short and/or long actuation of the rocker switch.
  • Page 29: Media Control, Cd Player

    Pos: 22.41 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/M - O/Mediensteuerung CD-Player @ 9\mod_1269500376630_15.doc @ 52849 @ 2 Media control, CD player Pos: 22.42 /KNX/Applikationsbeschreibungen/Display - GUI/Mediensteuerung CD-Player/App. - Mediensteuerung CD-Player - DIN-A4 @ 9\mod_1269499470874_15.doc @ 52844 @ A CD player can be remotely controlled via the bus using the "Media control, CD player" application. The symbols for "On/Off", "CD selection", "Player control"...
  • Page 30: Media Control, Radio

    KNX Technical Reference Manual ® Busch-priOn Pos: 22.44 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/M - O/Mediensteuerung Radio @ 9\mod_1269500818782_15.doc @ 52860 @ 2 Media control, radio Pos: 22.45 /KNX/Applikationsbeschreibungen/Display - GUI/Mediensteuerung Radio/App. - Mediensteuerung Radio - DIN-A4 @ 9\mod_1269500514614_15.doc @ 52855 @ A radio can be remotely controlled via the bus using the "Media control, radio"...
  • Page 31: Media Control, Video Player

    Pos: 22.47 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/M - O/Mediensteuerung Video-Player @ 9\mod_1269501501586_15.doc @ 52871 @ 2 Media control, video player Pos: 22.48 /KNX/Applikationsbeschreibungen/Display - GUI/Mediensteuerung Video-Player/App. - Mediensteuerung Video-Player - DIN-A4 @ 9\mod_1269500928769_15.doc @ 52866 @ 2 A CD player can be remotely controlled via the bus using the "Media control CD player" application. The symbols for "On/Off", "Player control"...
  • Page 32: Weekly Timer

    KNX Technical Reference Manual ® Busch-priOn Pos: 22.52 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/U - Z/Wochenschaltuhr @ 9\mod_1269504586283_15.doc @ 52893 @ 2 Weekly timer Pos: 22.53 /KNX/Applikationsbeschreibungen/Display - GUI/Wochenschaltuhr/App. - Wochenschaltuhr - DIN-A4 @ 9\mod_1269502016677_15.doc @ 52888 @ 2 With the "week timer" it is possible to call up defined switching times that are stored in the unit. Up to four different programs can be called up and edited by the user on the display via the push-button / rotary control element.
  • Page 33: Alarm Clock

    Pos: 22.55 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/U - Z/Wecker @ 9\mod_1269505094679_15.doc @ 52904 @ 2 Alarm clock Pos: 22.56 /KNX/Applikationsbeschreibungen/Display - GUI/Wecker/App. - Wecker - DIN-A4 @ 9\mod_1269504649733_15.doc @ 52899 @ 22 Alarm times (alarm clock times) can be defined with the "Alarm-clock" application. The times are set by the user with the push-button/rotary control element.
  • Page 34: Messages

    KNX Technical Reference Manual ® Busch-priOn Pos: 22.58 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/M - O/Meldungen @ 9\mod_1269505427898_15.doc @ 52915 @ 22 Messages Pos: 22.59 /KNX/Applikationsbeschreibungen/Display - GUI/Meldungen/App. - Meldungen - DIN-A4 @ 9\mod_1269505283373_15.doc @ 52910 @ 2 Messages can be shown on the display and acoustically signaled over the internal loudspeaker. These can be predefined system messages such as "Storage medium was removed"...
  • Page 35: Unit Blockage

    Pos: 22.63 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Gerätesperre @ 9\mod_1269507282299_15.doc @ 52987 @ 2 Unit blockage Pos: 22.64 /KNX/Applikationsbeschreibungen/Display - GUI/Geraetesperre/App. - Gerätesperre - DIN-A4 @ 9\mod_1269507196912_15.doc @ 52982 @ 22 The operation of the display from the circuit menu, or the call-up of individual functions, can be protected against unauthorised access by means of a PIN.
  • Page 36: Switch Actuator Application

    KNX Technical Reference Manual ® Busch-priOn Pos: 22.70 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Jalousieaktor @ 10\mod_1269514191049_15.doc @ 53234 @ 22 Shutting actuator Pos: 22.71 /KNX/Applikationsbeschreibungen/Applikationen - App/Jalousieaktor/App. - Jalousieaktor - DIN-A4 @ 10\mod_1269513864598_15.doc @ 53229 @ With the "Shutting actuator" application the shutting actuator is activated (Flush-type switch actuator 2-gang). It has two 1-bit communication objects "Move"...
  • Page 37: Movement Detector

    Pos: 22.75 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/A - F/Bewegungsmelder @ 15\mod_1289224598389_15.doc @ 96991 @ 222 Movement detector Pos: 22.76 /KNX/Applikationsbeschreibungen/Applikationen - App/Bewegungsmelder/App. - Bewegungsmelder - DIN-A4 @ 10\mod_1269849605442_15.doc @ 53303 @ The movement detector application can trigger telegrams on the bus when a movement is detected in the detection zone. Telegrams can also be sent on the bus when telegrams are received on the 1-bit communication object "External pushbutton input".
  • Page 38 KNX Technical Reference Manual ® Busch-priOn Motion sensor Object name Data type Flags Enable 1 Bit EIS1 / DPT 1.001 C, W, U Light-on time 2 Byte / DPT 7.005 C, W, U Extension unit input 1 Bit EIS1 / DPT 1.001 C, W, U Actuator status input 1 Bit EIS1 / DPT 1.001...
  • Page 39: Alarm Function

    Pos: 22.78 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/LED-Funktion @ 9\mod_1269508367126_15.doc @ 53030 @ 2 LED function Pos: 22.79 /KNX/Applikationsbeschreibungen/Applikationen - App/LED Funktion/App. - LED-Funktion - DIN-A4 @ 9\mod_1269508113996_15.doc @ 53025 @ With the "LED function" application, the LED of the rocker can be used for orientation lighting, for status indication or for function display.
  • Page 40 KNX Technical Reference Manual ® Busch-priOn Pos: 22.85 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/U - Z/Verzögerung @ 9\mod_1269509457458_15.doc @ 53093 @ 22 Delay Pos: 22.86 /KNX/Applikationsbeschreibungen/Applikationen - App/Verzögerung/App. - Verzögerung - DIN-A4 @ 9\mod_1269508848356_15.doc @ 53088 @ Telegrams can be received via the "Input" object using the "Delay" application. The telegrams received are sent out on the "Output"...
  • Page 41 Pos: 22.88 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Treppenhauslicht @ 9\mod_1269509802172_15.doc @ 53113 @ 22 Staircase lighting Pos: 22.89 /KNX/Applikationsbeschreibungen/Applikationen - App/Treppenhauslicht/App. - Treppenhauslicht - DIN-A4 @ 9\mod_1269509557128_15.doc @ 53098 @ With the "Staircase lighting" application, switching telegrams or value telegrams can be provided with a light-on time. Depending on the parameterisation, the application shows different communication objects: - a 1-bit object for input and output If an ON telegram is received via the "Input/Output"...
  • Page 42 KNX Technical Reference Manual ® Busch-priOn Pos: 22.91 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/G - L/Lichtszenenaktor @ 9\mod_1269510610443_15.doc @ 53133 @ 2 Light scene actuator Pos: 22.92 /KNX/Applikationsbeschreibungen/Applikationen - App/Lichtszenenaktor/App. - Lichtszenenaktor - DIN-A4 @ 9\mod_1269509871874_15.doc @ 53118 @ With the "Light scene actuator" application, it is possible to call up scenes that are stored in the device via the receipt of a scene number on the 1-byte communication object "Scene call-up".
  • Page 43 Pos: 22.96 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/P - R/Preset @ 10\mod_1269511326199_15.doc @ 53153 @ 2 Preset Pos: 22.97 /KNX/Applikationsbeschreibungen/Applikationen - App/Preset/App. - Preset - DIN-A4 @ 9\mod_1269511150514_15.doc @ 53148 @ The "Preset" application makes an input and output communication object available. At the receipt of a switching telegram on the 1-bit input object, a telegram is immediately sent out on the 1-byte output object.
  • Page 44 KNX Technical Reference Manual ® Busch-priOn Pos: 22.101 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/A - F/Blinken @ 10\mod_1269511888317_15.doc @ 53173 @ 2 Flashing Pos: 22.102 /KNX/Applikationsbeschreibungen/Applikationen - App/Blinken/App. - Blinken - DIN-A4 @ 10\mod_1269511782600_15.doc @ 53168 @ In order to trigger a flashing sequence on the output object, a telegram must be received on the input object beforehand. The "Flashing"...
  • Page 45 Pos: 22.106 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Tor @ 10\mod_1269512122627_15.doc @ 53183 @ 22 Gate Pos: 22.107 /KNX/Applikationsbeschreibungen/Applikationen - App/Tor/App. - Tor - DIN-A4 @ 10\mod_1269511957207_15.doc @ 53178 @ The "Gate" application allows specific signals to be filtered and the signal flow to be temporarily blocked. The function has three communication objects: "Control input", "Input"...
  • Page 46 KNX Technical Reference Manual ® Busch-priOn Pos: 22.109 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/M - O/Min- / Maxwertgeber @ 10\mod_1269512699231_15.doc @ 53194 @ 22 Min/Max value transducer Pos: 22.110 /KNX/Applikationsbeschreibungen/Applikationen - App/Min- Maxwertgeber/App. - Min- / Maxwertgeber - DIN-A4 @ 10\mod_1269512210610_15.doc @ 53189 @ Up to eight input values can be compared with each other using the "Min/max value transducer"...
  • Page 47 Pos: 22.112 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/S - T/Schwellwert / Hysterese @ 10\mod_1269513105197_15.doc @ 53204 @ 2 Threshold value / hysteresis Pos: 22.113 /KNX/Applikationsbeschreibungen/Applikationen - App/Schwellwert / Hysterese/App. - Schwellwert / Hysterese - DIN-A4 @ 10\mod_1269512775480_15.doc @ 53199 @ With the "Threshold value / Hysteresis" application, value telegrams can be received on an input communication object and compared with threshold values specified in the device.
  • Page 48 KNX Technical Reference Manual ® Busch-priOn Pos: 22.117 /Produkthandbuch - DIN-A4/Überschriften/2. Ebene/P - R/Priorität @ 10\mod_1269513770958_15.doc @ 53224 @ 2 Priority Pos: 22.118 /KNX/Applikationsbeschreibungen/Applikationen - App/Prioritaet/App. - Priorität - DIN-A4 @ 10\mod_1269513570444_15.doc @ 53219 @ The "Priority" application has 3 communication objects, a 1-bit object "Switch input", a 2-bit object "Input priority" and a 1-bit object "Output".
  • Page 49 KNX Technical Reference Manual | 0073-1-7388 | 49...
  • Page 50 Busch-Jaeger Elektro GmbH The detailed specifications agreed to at the time of PO box ordering apply to all orders. ABB accepts no 58505 Lüdenscheid responsibility for possible errors or incompleteness in this document. Freisenbergstraße 2 We reserve all rights to this document and the topics 58513 Lüdenscheid...