4
S C R E E N M A S T E R R V G 2 0 0 / PA P E R L E S S R E C O R D E R | C I/ R V G 2 0 0/0 0 1 - E N R E V. A
1 Locating the recorder
WARNING
• Locate the recorder in a position where its
temperature and humidity specification are not
exceeded and ensure it is suitably protected from
direct sunlight, rain, snow and hail.
• Select a location away from strong electrical and
magnetic fields. If this is not possible, particularly
in applications where mobile communications
equipment is expected to be used, screened cables
within flexible, earthed metal conduit must be
used.
Eye-level location
RVG200
Ambient temperature
RVG200
Humidity
RVG200
Avoid vibration
RVG200
Figure 1 Locating the recorder
50 °C
(122 °F)
Max.
0 °C
(32 °F)
Min.
5 to 95 %

2 Panel-mounting the recorder

Referring to Figure 2:
1 Cut the correct sized hole
2 Insert recorder
B
into the panel cut-out.
3 Fit upper and lower panel clamps
4 Tighten the clamping screws
torque of 0.2 Nm (1.77 lbf.in).
CAUTION
Correct tightening of the clamping screws is critical
to ensure proper compression of the panel seal and
achieve the IP66 / NEMA 4X hose-down rating.
Panel mounting dimensions – mm (in.)
138.0
+1
– 0
(5.43
+0.04
)
– 0
30 (1.18) min.
Figure 2 Panel-mounting the recorder
A
in the panel.
C
to the recorder.
evenly and securely to a
D
30 (1.18) min.
138.0
+1
– 0
(5.43
+0.04
)
– 0