WIRING
Where a tilde "~" symbol appears, substitute the slot position of the module. Where a number sign "#" appears,
substitute the contact number.
For high-density input/output modules 6W and 6X, use the following guidelines to connect:
12 to 24 AWG (3.3 mm
16 to 24 AWG (1.31 mm
maximum per circuit.
3
Suggested wiring screw tightening torque is a minimum 4.43 in-lb (0.5 Nm) and maximum 5.31 in-lb (0.6 Nm)
Minimum suggested temperature rating for the conductors is 75°C
Wire type: copper
Do not use with SL power supply module
Table 3-3: Contact input and output module assignments
~6A module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-C
~4
Form-C
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6E module
Terminal
Output or
assignment
input
~1
Form-C
~2
Form-C
~3
Form-C
~4
Form-C
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6K module
Terminal
Output
assignment
~1
Form-C
~2
Form-C
3-20
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, give the
FlexLogic operand driving the contact output a reset delay of 10 ms to prevent damage of the output
contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
2
2
to 0.2 mm
), single wire termination
2
2
to 0.2 mm
), multiple wire termination with matching wire sizes and stranding. Two wires
~6B module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-C
~4
Form-C
~5
Form-C
~6
Form-C
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6F module
Terminal
Output
assignment
~1
Fast Form-C
~2
Fast Form-C
~3
Fast Form-C
~4
Fast Form-C
~5
Fast Form-C
~6
Fast Form-C
~7
Fast Form-C
~8
Fast Form-C
~6L module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~6C module
Terminal
Output
assignment
~1
Form-C
~2
Form-C
~3
Form-C
~4
Form-C
~5
Form-C
~6
Form-C
~7
Form-C
~8
Form-C
~6G module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-A
~4
Form-A
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6M module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
~6D module
Terminal
Output
assignment
~1a, ~1c
2 Inputs
~2a, ~2c
2 Inputs
~3a, ~3c
2 Inputs
~4a, ~4c
2 Inputs
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6H module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-A
~4
Form-A
~5
Form-A
~6
Form-A
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6N module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A