CHAPTER 5: SETTINGS
The D30 is provided with this optional feature, specified as an option at the time of ordering. Using the order
code for your device, see the order codes in chapter 2 for details.
User-programmable pushbuttons provide an easy and error-free method of entering digital state (on, off) information. The
number depends on the front panel ordered.
Enhanced horizontal front panel — 16 user-programmable pushbuttons
Enhanced vertical front panel — 6 user-programmable pushbuttons
Standard horizontal front panel — 12 user-programmable pushbuttons
Graphical front panel — 16 user-programmable pushbuttons (eight physical pushbuttons, eight graphical interface
pushbuttons)
User-programmable pushbuttons require a front panel with that option. If the front panel was ordered separately,
update the EnerVista software under Maintenance > Change Front Panel.
The digital state can be entered locally (by directly pressing the front panel pushbutton or optional graphical front panel
interface) or remotely (via FlexLogic operands) into FlexLogic equations, protection elements, and control elements. Typical
applications include breaker control, autorecloser blocking, and setting groups changes. For example, set pushbuttons 1 to
5 to select settings groups 1 to 5, or set pushbutton 1 to clear event records. The user-programmable pushbuttons are
under the control level of password protection.
Example
To clear event records using pushbutton 1, set Settings > Product Setup > Clear Relay Records > Clear Event Records to
FlexLogic operand
PUSHBUTTON 1
Programmable Pushbuttons > Pushbutton 1 Function to "Self-reset." For a graphical front panel, to use a side
pushbutton 9 to 16 to clear the event records, it also needs to be programmed in a single-line diagram.
The figures show user-configurable pushbuttons for the front panels.
Figure 5-54: User-programmable pushbuttons (enhanced front panel)
Figure 5-55: User-programmable pushbuttons (standard front panel)
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
ON. Then program the pushbutton by setting Settings > Product Setup > User-
PRODUCT SETUP
5
5-125