CHAPTER 5: SETTINGS
Table 5-20: D30 FlexLogic operands
Operand type
Operand syntax
ANNUNCIATOR
ANY ANCTR ABNORMAL
Graphical front panel
ANY ANCTR ALARMED
CONTROL
CONTROL PUSHBTN 1 ON
PUSHBUTTONS
CONTROL PUSHBTN 2 ON
Enhanced and
CONTROL PUSHBTN 3 ON
standard front panels
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
CYBERSENTRY
ROLE ADMIN ACT
ROLE SUPERVISOR ACT
ROLE ENGINEER ACT
ROLE OPERATOR ACT
ROLE OBSERVER ACT
AUTHENTICATION FAIL
UNAUTH FW ATTEMPT
UNAUTH SETTING WRITE
DIRECT DEVICES
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIRECT INPUT/
DIR IO CH1 CRC ALARM
OUTPUT CHANNEL
MONITORING
DIR IO CH2 CRC ALARM
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
ELEMENT:
AR1 ENABLED
Autoreclose
AR1 RIP
(per CT bank)
AR1 LO
AR1 BLK FROM MAN CLS
AR1 CLOSE
AR1 SHOT CNT=0
AR1 SHOT CNT=1
AR1 SHOT CNT=2
AR1 SHOT CNT=3
AR1 SHOT CNT=4
AR1 DISABLED
ELEMENT:
AUX OV1 PKP
Auxiliary overvoltage
AUX OV1 DPO
AUX OV1 OP
ELEMENT:
AUX UV1 PKP
Auxiliary
AUX UV1 DPO
undervoltage
AUX UV1 OP
AUX UV2 to 3
ELEMENT:
BKR ARC 1 OP
Breaker arcing
BKR ARC 1 DPO
BKR ARC 1 MAX OP
BKR ARC 1 MAX DPO
BKR ARC 2 OP
BKR ARC 2 DPO
BKR ARC 2 MAX OP
BKR ARC 2 MAX DPO
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Operand description
On for one second when any annunciator window state changes from
normal to abnormal
On while any annunciator window state is abnormal
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Administrator role is active and is set to true when that is the case
Supervisor role is active and is set to true when that is the case
Engineer role is active and is set to true when that is the case
Operator role is active and is set to true when that is the case
Observer role is active and is set to true when that is the case
Operand set for Failed Authentication self-test and alarm
Operand set for firmware lock self-test and alarm
Operand set for settings lock self-test and alarm
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level
The rate of returned direct input/output messages on channel 1 exceeded
the user-specified level (ring configurations only)
The rate of returned direct input/output messages on channel 2 exceeded
the user-specified level (ring configurations only)
Autoreclose 1 is enabled
Autoreclose 1 is in progress
Autoreclose 1 is locked out
Autoreclose 1 is temporarily disabled
Autoreclose 1 close command is issued
Autoreclose 1 shot count is 0
Autoreclose 1 shot count is 1
Autoreclose 1 shot count is 2
Autoreclose 1 shot count is 3
Autoreclose 1 shot count is 4
Autoreclose 1 is disabled
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
Auxiliary undervoltage element has picked up
Auxiliary undervoltage element has dropped out
Auxiliary undervoltage element has operated
Same set of operands as shown for AUX UV1
Breaker arcing current 1 has operated
Breaker arcing current 1 has dropped out
Breaker arcing current 1 max interrupting current has operated
Breaker arcing current 1 max interrupting current has dropped out
Breaker arcing current 2 has operated
Breaker arcing current 2 has dropped out
Breaker arcing current 2 max interrupting current has operated
Breaker arcing current 2 max interrupting current has dropped out
FLEXLOGIC
5
5-167