CHAPTER 5: SETTINGS
enables phase selection supervision on phase distance zone 1 to zone 3.
PH DIST PH SELECT SUPV
5.7.4.2 Phase distance (ANSI 21P, IEC PDIS)
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) DISTANCE PHASE DISTANCE Z1(Z5)
PHASE DISTANCE Z1
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 5-98: Memory voltage logic
PHS DIST Z1
FUNCTION: Disabled
PHS DIST Z1 DIR:
Forward
PHS DIST Z1
SHAPE: Mho
PHS DIST Z1 XFMR VOL
CONNECTION: None
PHS DIST Z1 XFMR CUR
CONNECTION: None
PHS DIST Z1
REACH: 2.00 Ω
PHS DIST Z1
RCA: 85°
PHS DIST Z1 REV
REACH: 2.00 Ω
PHS DIST Z1 REV
REACH RCA: 85°
PHS DIST Z1
COMP LIMIT: 90°
PHS DIST Z1
DIR RCA: 85°
PHS DIST Z1
DIR COMP LIMIT: 90°
PHS DIST Z1 QUAD
RGT BLD: 10.00 Ω
PHS DIST Z1 QUAD
RGT BLD RCA: 85°
PHS DIST Z1 QUAD
LFT BLD: 10.00 Ω
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: Forward, Reverse, Non-directional
Range: Mho, Quad
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
Range: None, Dy1, Dy3, Dy5, Dy7, Dy9, Dy11, Yd1,
Yd3, Yd5, Yd7, Yd9, Yd11
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 30 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
Range: 60 to 90° in steps of 1
Range: 0.02 to 500.00 ohms in steps of 0.01
5
5-193