Connecting The Battery Supply - Huawei ETP4830-A1 User Manual

Hide thumbs Also See for ETP4830-A1:
Table of Contents

Advertisement

ETP4830-A1
User Manual
Step 7 Set the SNMP trap destination address and trap port.
Step 8 Upload the MIB libraries HUAWEI-MIB.mib and HUAWEI-SITE-MONITOR-MIB.mib
to the NMS.
----End

6.9 Connecting the Battery Supply

Prerequisites
To avoid damage to batteries, switch on the battery circuit breaker only after correctly setting
the battery parameters.
Procedure
Step 1 Switch off the AC circuit breaker for the upper-level device, and then switch on the battery
circuit breaker on PDU.
Step 2 Switch on the AC circuit breaker for the upper-level device, and then switch on the load
circuit breakers on PDU.
Issue 06 (2014-02-20)
Figure 6-3 SNMPv3 parameters
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
6 Commissioning
39

Hide quick links:

Advertisement

Table of Contents
loading