User Manual
Figure 4-9 Connecting the load cable
----End
4.3.5 Connecting the Battery Cable
Connecting battery cables is similar to connecting load cables. For details, see
Connecting the DC Load
4.3.6 Connecting the AC Input Power Cable
Before connecting the AC input power cable:
Connecting the Single-Phase AC Input Power Cable
Procedure
Step 1 Remove the protective cover over AC input terminals.
Step 2 Connect the neutral wire (an M4 OT terminal is used for the cable) to the N wiring terminal.
Step 3 Connect the live wire (an M4 OT terminal is used for the cable) to the L wiring terminal.
Issue 06 (2014-02-20)
Cable.
Install a circuit breaker for upper-level device to protect the power system.
Switch the corresponding circuit breaker for the upper-level device to OFF.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.