CONFIG / GENERAL
POLL
LOC
LCD
ADDR
KEYS D I SP
LOCA L KEYS CONTROL
[ E n a b l e
]
N E X T L A S T
L K E Y
L K E Y
L C D
D I S P L A Y
[ P V a n d % o f
N E X T L A S T
M O D E M O D E
CONFIGURATION
CHNG
XMTR
GEN
I / O
I NFO
CONF
DATABASE OPERATIONS
TAG
SAVE
SEND
LIST
CONF
CONF
F T 1 0 0
L T 1 1 2
P T 2 3 4
K . S C
N E X T
T A G S
DATABASE OPERATIONS
TAG
SAVE
SEND
LIST
CONF
CONF
C o n f i g u r a t i o n s a v e d
P r e s s
a n y
k e y
t o
c o n t i n u e
DATABASE OPERATIONS
TAG
SAVE
SEND
LIST
CONF
CONF
W A R N I N G - C o n t r o l l o o p
s h o u l d b e i n M A N U A L
For 600T and 600T EN Transmitters:
For the 600T transmitters the General Configuration menu allows two
further selection: Local Keys Control and LCD Display Mode: the
relevant display are shown aside.
The Local Keys Control allows to enable or disable the zero and span
calibration devices fitted in the transmitters. Pressing F2 select this option
E N T R
and using F1 or F2 select Enable or Disable and then press the F4 key.
The LCD Display Mode allows to define the variables to be displayed in
M O D E
the LCD Local display (if fitted). Four selection are possible: Process
r a n g e ]
Variables, PV and output, Percent of range, PV and % of range. Select
E N T R
the required option and then press F4 to Enter the selection. Press ESC
to leave the procedure.

CONF - Database operations - TAG LIST option

As mentioned before The Hand Held Communicator can store up to 32
transmitter configurations in his non-volatile memory, having the ability of
DBASE
saving , down-loading and cloning ( duplicating ) these configurations.
MEM
The configurations stored in the Communicator memory are identified by
their Tag name.
From the Configuration Main Menu, pressing F4 ( DBASE MEM ) the
DELET
Database Operations Main Menu appears. Pressing F1 ( TAG LIST ) the
CONF
following display appears, showing the list of the configurations saved in
the Communicator.
Each display contains up to four tags: if more tags are included in the list
the label NEXT TAGS on F1 permits the next page of the list. When the
end of the list is reached, the list will be repeated. Use ESCAPE to return
to the Database Main Menu.

CONF - Database operations - SAVE CONFIGURATION option

From the Database Main Menu, pressing F2 ( SAVE CONF ) , the
configuration data and parameters of the connected transmitter are
saved in the Communicator Database and the following display appears
DELET
(See Appendix "D" for the list of transmitter's data saved in database).
CONF
If that tag already exists in the database, a message is issued: TAG
ALREADY EXIST in this case it is necessary to delete the existing tag
from the database in order to save the new one. If no slots are available
in the database memory for storing the configuration, a warning message
appears declaring: " Database memory full".Use ESCAPE to return to the
Database Main Menu.

CONF - Database operations - SEND CONFIGURATION option

This option permits to send a configuration stored in the Database
memory of the Communicator to a connected transmitter. Note that only
the data and parameters necessary to configure a transmitter are sent.
DELET
CONF
The selection of the configuration to be sent can be made from the list of
the stored configurations.
WARNING - Maximum attention MUST be given to this operation.
P R O
Ensure that the configuration to send is suitable for the transmitter
C E E D
application and the connected controller is in manual status.
Not following these precautions could result in dangerous situations
with effects on personal injury or property damage.