Topic Generator - ABB COM600S User Manual

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

3.4.9.
70
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
High
0
High-High
0
Low
0
Low-Low
0
Max
20000
Min
0
Neutral Limit Value
Supervision
Neutral High
0
Neutral High-High
0
Neutral Low
0
Neutral Low-Low
0
Neutral Max
20000
Neutral Min
0

Topic Generator

When data objects have been configured with addresses, use the Topic Generator function
to specify how data is requested from devices. A topic definition for an indication address
specifies start and end of address, data format, deadband, and polling interval in milli-
seconds. However, a topic definition for a controllable point only specifies address range
and its data format
To generate topic definitions:
1. Select the Communication tab on the Project Explore window.
2. Right-click a OPC Server node or a IED node and select the Topic Generator function
on the context menu.
In most cases, modifications to the automatically generated topics are not required.
However, some topic definitions may need to be changed, polling interval for example,
for some devices to work properly.
Description
High limit measurement. Event is created,
when value crosses the limit.
High-high limit for measurement. Event is
created, when value crosses the limit.
Low limit for measurement. Event is cre-
ated, when value crosses the limit.
Low-low limit for measurement. Event is
created, when value crosses the limit.
Maximum value for measurement.
Minimum value for measurement.
High limit for measurement. Event is cre-
ated, when value crosses the limit.
High-high limit for measurement. Event is
created, when value crosses the limit.
Low limit for measurement. Event is cre-
ated, when value crosses the limit.
Low-low limit for measurement. Event is
created, when value crosses the limit.
Maximum value for measurement.
Minimum value for measurement.