ABB COM600S User Manual page 35

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

1MRS756445
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
61850-Type
CMV
Sub Type
Sub Type
MV/CMV simple
MV_LIMIT_CHECK
Default: MV/CMV simple
Addresses
Measurement
Default
Format
Word
Integer
Long MSW first
Long MSW last
Float MSW first
Float MSW last
Bit
Default: Word
Measurement
0 to 65535
Register
Default: 0
Scale and Unit
Multiplier
Default: Deka
Scale
Default: None
Unit
Default: Dimensionless
Limit Value Super-
vision
Max
20000
Min
0
Description
61850-Type
Sub type for MV/CMV.
Data format of the value.
Holding or input register address for the
measurement. Holding register (4X refer-
ence) address range 40001 to 49999 or
input register (3X reference) address
range 30001 to 39999. Address 0 equals
to no information available. If format
requiring two registers is used, then the
lower address must be entered.
Specifies the multiplier for current SI unit.
Scale used with this type.
SI unit for measurement as described in
IEC61850.
Maximum value for measurement.
Minimum value for measurement.
35