1MRS756445
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
Fail Indication
0 to 65535
Coil/Input
Default: 0
Open Command
0 to 65535
Type
Default: 0
Open Control Coil
0 to 655359
Default: 0
Open Indication
0 to 65535
Coil/Input
Default: 0
Table 3.4.8.8-2 Configurable DPC properties for OPC servers with Modbus device,
subtype GENERIC_CONTROL
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
DPC
Subtype
GENERIC_CONTROL
Addresses
Address for pass-
0 to 65535
word 1
Up to 4 ASCII Characters Left-
most Digits
Address for pass-
0 to 65535
word 2
Up to 4 ASCII Characters
rightmost Digits
Password 1
Default: empty string.
Password 2
Default: empty string.
Description
Coil or input address for the fail indication
(optional). Coil (0X reference) address
range 1 to 9999 or input (1X reference)
address range 10001 to 19999. Address
0 equals to no information available.
Open command type.
Coil address for the open control. Coil (0X
reference) address range 1 to 9999.
Address 0 equals to no information avail-
able.
Coil or input address for the open indica-
tion. Coil (0X reference) address range 1
to 9999 or input (1X reference) address
range 10001 to 19999. Address 0 equals
to no information available.
Description
61850-Type
starting address of password 1
Starting address of password 2
IED device password. Default is empty
string. This password is written to up to 2
register starting from the one specified
from Address for password 1.
Example: 1234
IED device password. Default is empty
string. This password is written to up to 2
register starting from the one specified
from Address for password 2.
Example: 1234