1MRS756445
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
Phase AB Mag-
Default
nitude Format
Word
Integer
Long MSW first
Long MSW last
Float MSW first
Float MSW last
Bit
Default: Word
Phase BC
Addresses
Phase BC Angle
0 to 65535
Default: 0
Phase BC Angle
Default
Format
Word
Integer
Long MSW first
Long MSW last
Float MSW first
Float MSW last
Bit
Default: Word
Phase BC Mag-
0 to 65535
nitude
Default: 0
Description
Data format for phase AB magnitude.
Holding or input register address for the
phase BC angle. Holding register (4X ref-
erence) address range 40001 to 49999 or
input register (3X reference) address
range 30001 to 39999. Address 0 equals
to no information available.
Data format for phase BC angle.
Holding or input register address for the
phase BC magnitude. Holding register (4X
reference) address range 40001 to 49999
or input register (3X reference) address
range 30001 to 39999. Address 0 equals
to no information available.
37