CHAPTER 6: ACTUAL VALUES
There is an identical menu for each of the breakers.
The
values are in units of kA
BKR 1 ACC ARCING AMP
breaker arcing current records.
The
BREAKER OPERATING TIME
All of the values are stored in non-volatile memory and retained with power cycling.

6.6 Product information

6.6.1 Model information

ACTUAL VALUES  PRODUCT INFO  MODEL INFORMATION
 MODEL INFORMATION
The order code, serial number, Ethernet MAC address, date and time of manufacture, and operating time are shown here.
The rear panel on the device contains similar information.
— UR devices with firmware 7.0x and above have three Ethernet ports that can be used on three
ETHERNET MAC ADDRESS
networks. The MAC address displays for port 1. The MAC address for port 2 is one higher. The MAC address for port 3 is one
higher than port 2. In redundant mode, the MAC addresses for ports 2 and 3 are the same as port 2.

6.6.2 Firmware revisions

6.6.2.1 Enhanced and standard front panels
ACTUAL VALUES  PRODUCT INFO  FIRMWARE REVISIONS
 FIRMWARE REVISIONS
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
2
-cycles. See the
is defined as the slowest operating time of breaker poles that were initiated to open.
ORDER CODE LINE 1:
L30-A00-AAA-A0A-A0A-
ORDER CODE LINE 2:
A0A-A0A-A0A
ORDER CODE LINE 3:
ORDER CODE LINE 4:
SERIAL NUMBER:
ETHERNET MAC ADDRESS
000000000000
MANUFACTURING DATE:
OPERATING TIME:
0:00:00
PMU FEATURE ACTIVE:
No
CT/ VT ADVANCED DIAG
ACTIVE: No
LAST SETTING CHANGE:
1970/01/01 23:11:19
L30 Relay
REVISION: 7.6x
COMMANDS  CLEAR RECORDS
Range: standard GE order code format
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: standard GE serial number format
Range: standard Ethernet MAC address format
Range: YYYY/MM/DD HH:MM:SS
Range: operating time in HH:MM:SS
Range: Yes, No
Range: Yes, No
Range: YYYY/MM/DD HH:MM:SS
Range: 0.00 to 655.35
Revision number of the application firmware.