CONTROL ELEMENTS
5.8.7 Synchrocheck (ANSI 25)
SETTINGS CONTROL ELEMENTS SYNCHROCHECK SYNCHROCHECK 1(4)
5
SYNCHROCHECK 1
5-272
Figure 5-143: Frequency rate of change logic
SYNCHK1 FUNCTION:
Disabled
SYNCHK1 BLOCK:
Off
SYNCHK1 V1 SOURCE:
SRC 1
SYNCHK1 V2 SOURCE:
SRC 2
SYNCHK1 MAX VOLT
DIFF: 10000 V
SYNCHK1 MAX ANGLE
DIFF: 30°
SYNCHK1 MAX FREQ
DIFF: 1.00 Hz
Range: Disabled, Enabled
Range: FlexLogic operand
Range: SRC 1, SRC 2
Range: SRC 1, SRC 2
Range: 0 to 400000 V in steps of 1
Range: 0 to 100° in steps of 1
Range: 0.00 to 2.00 Hz in steps of 0.01
L30 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS