5.7 INPUTS / OUTPUTS
!"
PATH: SETTINGS
INPUTS/OUTPUTS
# REMOTE OUTPUTS
# UserSt- 1 BIT PAIR
Remote Outputs 1 to 32 originate as GOOSE messages to be transmitted to remote devices. Each digital point in the mes-
sage must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GOOSE messages when there has been no change of state of
any selected digital point. This setting is located in the
tings menu.
For more information on GOOSE specifications, see REMOTE INPUTS/OUTPUTS – OVERVIEW in the
REMOTE DEVICES section.
NOTE
!"
PATH: SETTINGS
INPUTS/OUTPUTS
5
# RESETTING
#
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic™ latches) to the reset
state. The RESET command can be sent from the faceplate RESET button, a remote device via a communications chan-
nel, or any programmed operand.
When the RESET command is received by the relay, two FlexLogic™ operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the FlexLogic™ operand "RESET OP". Each individual source of a RESET command also creates its individual oper-
and RESET OP (PUSHBUTTON), RESET OP (COMMS) or RESET OP (OPERAND) to identify the source of the
command. The setting shown above selects the operand that will create the RESET OP (OPERAND) operand.
5-92
!"
REMOTE OUTPUTS UserSt BIT PAIRS
UserSt- 1 OPERAND:
Off
UserSt- 1 EVENTS:
MESSAGE
Disabled
DEFAULT GOOSE UPDATE
TIME: 60 s
!"
RESETTING
RESET OPERAND:
Off
C60 Breaker Management Relay

5.7.9 REMOTE OUTPUTS: UserSt BIT PAIRS

!
REMOTE OUTPUTS UserSt- 1 BIT PAIR
Range: FlexLogic™ operand
Range: Disabled, Enabled
!"
PRODUCT SETUP
COMMUNICATIONS
Range: 1 to 60 s in steps of 1
Range: FlexLogic™ operand
5 SETTINGS
!"
set-
UCA/MMS PROTOCOL
5.7.10 RESETTING