METERING
6.3.4 Tracking frequency
ACTUAL VALUES METERING TRACKING FREQUENCY
TRACKING FREQUENCY
The tracking frequency displays here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE
System section of chapter 5 for details.
6.3.5 FlexElements
ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(8)
FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-2: FlexElement base units
Base unit
BREAKER ARCING AMPS
(Brk X Arc Amp A, B, and C)
DCmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
6
SOURCE ENERGY
(Positive and Negative Watthours,
Positive and Negative Varhours)
SOURCE POWER
SOURCE VOLTAGE
SYNCHROCHECK
(Max Delta Volts)
6.3.6 RxGOOSE analogs
ACTUAL VALUES METERING RxGOOSE Analogs
RxGOOSE
Analogs
The C60 is provided with optional GOOSE communications capability. This feature is specified as a
software option at the time of ordering. See the Order Codes section of chapter 2 for details.
The RxGOOSE Analog values display in this menu. The RxGOOSE Analog values are received via IEC 61850 GOOSE
messages sent from other devices.
6-20
TRACKING FREQUENCY
60.00 Hz
setting in the
SETTINGS SYSTEM SETUP POWER SYSTEM
FLEXELEMENT 1
OpSig: 0.000 pu
Description
2
cycle
BASE = 2000 kA
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
f
= 1 Hz
BASE
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
E
= 10000 MWh or MVAh, respectively
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
V
= maximum primary RMS value of all the sources related to the +IN and –IN inputs
BASE
RxGOOSE Analog 1
0.000
RxGOOSE Analog 32
0.000
I
for the +IN and –IN inputs
BASE
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
menu. See the Power