GE c60 Instruction Manual page 267

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
This section contains basic Phasor Measurement Unit (PMU) data, such as functions, source settings, and names.
— This setting enables the LOGICAL Device PMU 1 functionality. Use this setting to permanently enable or
PMU 1 FUNCTION
disable the feature.
— This setting assigns a numerical ID to the PMU. It corresponds to the IDCODE field of the data,
PMU 1 IDCODE
configuration, header, and command frames of the IEEE C37.118 protocol. The PMU uses this value when sending data,
configuration, and header frames; and it responds to this value when receiving the command frame. This is used when
only data from one PMU is present.
— This setting assigns an alphanumeric ID to the PMU station. It corresponds to the STN field of the
PMU 1 STN
configuration frame of the IEEE C37.118 protocol. This value is a 16-character ASCII string as per the IEEE C37.118
standard.
— This setting specifies one of the available C60 signal sources for processing in the PMU. Any
PMU 1 SIGNAL SOURCE
combination of voltages and currents can be configured as a source. The current channels can be configured as sums of
physically connected currents. This facilitates PMU applications in breaker-and-a-half, ring-bus, and similar arrangements.
The PMU feature calculates voltage phasors for actual voltage (A, B, C, and auxiliary) and current (A, B, C, and ground)
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
PMU 1 PHS-1:
NAME: GE-UR-PMU-PHS-1
PMU 1 PHS-14:
Off
PMU 1 PHS-14:
NAME: GE-UR-PMU-PHS-14
PMU 1 A-CH-1:
Off
PMU 1 A-CH-1:
NAME: AnalogChannel1
PMU 1 A-CH-16 (16):
Off
PMU 1 A-CH-16 (16):
NM: AnalogChannel16
PMU 1 D-CH-1:
Off
PMU 1 D-CH-1
NAME: DigChannel1
PMU 1 D-CH-1
NORMAL STATE: Off
PMU 1 D-CH-16:
Off
PMU 1 REC D-CH-16:
NM: DigChannel16
PMU 1 REC D-CH-16:
NORMAL STATE: Off
 37.118 PMU 1
 CONFIGURATION
 90-5 PMU 1
 CONFIGURATION
Range:
16-character ASCII string
Range:
available synchrophasor values
Range:
16-character ASCII string
Range:
available FlexAnalog values
Range:
16-character ASCII string
Range:
available FlexAnalog values
Range:
16-character ASCII string
Range:
available FlexLogic operands
Range:
16-character ASCII string
Range:
Off, On
Range:
FlexLogic operand
Range:
16-character ASCII string
Range:
Off, On
See below
See below
SYSTEM SETUP
5
5-141