GE c60 Instruction Manual page 270

Breaker protection system
Hide thumbs Also See for c60:
Table of Contents

Advertisement

SYSTEM SETUP
5.5.7.10 PMU calibration
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PHASOR MEASUREMENT UNIT 1  PMU 1(2)
CALIBRATION
 PMU 1
 CALIBRATION
5
This menu contains user angle and magnitude calibration data for the Phasor Measurement Unit (PMU). This data is
combined with the factory adjustments to shift the phasors for better accuracy.
PMU 1 VA... IG CALIBRATION ANGLE
sources, and they allow the user to calibrate each channel (four voltages and four currents) individually to offset errors
introduced by VTs, CTs, and cabling. The setting values are effectively added to the measured angles. Therefore, enter a
positive correction when the secondary signal lags the true signal and a negative value when the secondary signal leads
the true signal.
5-144
PMU 1 VA CALIBRATION
°
ANGLE: 0.00
PMU 1 VA CALIBRATION
MAG: 100.0%
PMU 1 VB CALIBRATION
ANGLE: 0.00°
PMU 1 VB CALIBRATION
MAG: 100.0%
PMU 1 VC CALIBRATION
ANGLE: 0.00°
PMU 1 VC CALIBRATION
MAG: 100.0%
PMU 1 VX CALIBRATION
ANGLE: 0.00°
PMU 1 VX CALIBRATION
MAG: 100.0%
PMU 1 IA CALIBRATION
ANGLE: 0.00°
PMU 1 IA CALIBRATION
MAG: 100.0%
PMU 1 IB CALIBRATION
ANGLE: 0.00°
PMU 1 IB CALIBRATION
MAG: 100.0%
PMU 1 IC CALIBRATION
ANGLE: 0.00°
PMU 1 IC CALIBRATION
MAG: 100.0%
PMU 1 IG CALIBRATION
ANGLE: 0.00°
PMU 1 IG CALIBRATION
MAG: 100.0%
PMU 1 SEQ VOLT SHIFT
ANGLE: 0°
PMU 1 SEQ CURR SHIFT
ANGLE: 0°
— These settings recognize applications with protection class voltage and current
Range:
–5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –5.00 to 5.00° in steps of 0.05
Range: 95.0 to 105.0 in steps of 0.1%
Range: –180 to 180° in steps of 30
Range: –180 to 180° in steps of 30
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents