CHAPTER 5: SETTINGS
where
T = Operate Time (in seconds)
TDM = Multiplier setting
I = Input Current
I
= Pickup Current setting
pickup
T
= Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
RESET
Recloser curves
The C60 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurve section in this
chapter for details.
5.7.3.3 Phase time overcurrent (ANSI 51P, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE TOC1(6)
 PHASE TOC 1
The phase time overcurrent element can provide a desired time-delay operating characteristic versus the applied current
or be used as a simple definite time element. The phase current input quantities can be programmed as fundamental
phasor magnitude or total waveform RMS magnitude as required by the application.
Two methods of resetting operation are available: "Timed" and "Instantaneous" (see the Inverse TOC Curve Characteristics
section earlier for details on curve setup, trip times, and reset operation). When the element is blocked, the time
accumulator resets according to the reset characteristic. For example, if the element reset characteristic is set to
"Instantaneous" and the element is blocked, the time accumulator is cleared immediately.
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
PHASE TOC1
FUNCTION: Disabled
PHASE TOC1 SIGNAL
SOURCE: SRC 1
PHASE TOC1
INPUT: Phasor
PHASE TOC1
PICKUP: 1.000 pu
PHASE TOC1
CURVE: IEEE Mod Inv
PHASE TOC1
TD MULTIPLIER: 1.00
PHASE TOC1
RESET: Instantaneous
PHASE TOC1 VOLTAGE
RESTRAINT: Disabled
PHASE TOC1 BLOCK A:
Off
PHASE TOC1 BLOCK B:
Off
PHASE TOC1 BLOCK C:
Off
PHASE TOC1
TARGET: Self-reset
PHASE TOC1
EVENTS: Disabled
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4
Range: Phasor, RMS
Range: 0.000 to 30.000 pu in steps of 0.001
Range: see Overcurrent Curve Types table
Range: 0.00 to 600.00 in steps of 0.01
Range: Instantaneous, Timed
Range: Disabled, Enabled
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5