SYSTEM SETUP
5.5.7.14 Control blocks
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  IEC 90 – 5 MSVCB01 CONFIGURATION
 IEC 90-5 MSVCB
 CONFIGURATION
5
— The SV Stream Control is set by either toggling an assigned FlexLogic operand or a remote client write, to
MSVCB 1 SVENA
start and stop the streaming of R-SV frames. If remote client control is disabled, a negative response is provided to the
client in response to a write attempt. A FlexLogic operand (SvEna) is provided for each Aggregator that reflects the state of
the SvEna control where "1"= Enabled and "0"=Disabled. The figure shows the logic for setting the SvEna control bit.
MSVCB 1 CLIENT CONTRL
operand is a logic 1 state, remote clients can write to both the reserve bit and the SvEna bit. When the FlexLogic operand
is a logic 0 state, the remote client writes to the reserve bit, the SvEna is rejected by the UR, and a negative response with
the appropriate Service Error is returned to the client.
MSVCB 1 SVENA DEFLT
5-154
MSVCB 1 SVENA:
OFF
MSVCB 1 CLIENT CTRL:
OFF
MSVCB 1 SVENA DEFLT:
OFF
MSVCB 1 CONFREV:
1
MSVCB 1 PRIORITY:
4
MSVCB 1 IP CLASS:
46
MSVCB 1 VID:
0
MSVCB 1 APPID:
0
MSVCB 1 DEST. IP:
224.0.0.0
MSVCB 1 SECURITY:
0
Figure 5-75: Logic for setting SvEna control bit
— This setting determines if a client can write to the reserve bit. When the assigned FlexLogic
— This setting sets the default state of the stream (On or Off) on power-up or restart.
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1 to 4294967295
Range: 0 to 7
Range: 0 to 252
Range: 0 to 4095
Range: 0 to 16383
Range: 0 to 255.255.255.255
Range: 0 to 2
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS