4 PROGRAMMING
If the test is attempted while current is present, the setpoint will be forced to NORMAL MODE
and the following flash message will be displayed for 3 seconds.
If 6 7(67,1*? &855(17 6,08/$7,21?6,08/$7,21 is 21 , the setpoint will be forced to NORMAL
MODE and the following flash message will be displayed for 3 seconds.
If testing is attempted via the serial port while phase or ground current is present or simulation
mode is on, an error code will be returned.
While the 23(5$7,21 7(67 setpoint is displayed, use the
desired output relay and/or status indicator to be tested. As long as the test message remains
displayed the respective output relay and/or status indicator will be forced to remain energized.
As soon as a new message is selected, the respective output relay and/or status indicator return
to normal operation.
As a safeguard, relay and LED test will turn off automatically if:
power to the 239 is turned off and on
phase or ground current is detected by the 239
current simulation is turned on
new message is displayed
c) CURRENT SIMULATION
Simulated currents can be forced instead of the actual currents sensed by the external CTs con-
nected to the 239. This allows verification of all current related relay functions such as timed over-
load trip. It also allows verification that external trip and alarm wiring is responding correctly.
SIMULATION: Enter the required simulation phase and ground currents in the following mes-
sages. Enter ON to switch from actual currents to the programmed simulated values. This com-
mand will be ignored if real phase or ground current is present. Set this setpoint 2)) after
simulation is complete. As a safeguard, simulation will automatically turn off if:
real phase or ground current is detected while in simulation mode
power to the 239 is turned off and on
time programmed in the 6 7(67,1*?&855(17 6,08/$7,21?6,08/$7,21 (1$%/(' )25 setpoint
has elapsed since simulation was first enabled
239 is tripped
When current simulation is turned on the following flash message will be displayed for 3 seconds.
When current simulation is turned off the following flash message will be displayed for 3 seconds.
GE Multilin
Courtesy of NationalSwitchgear.com
RELAY TEST BLOCKED
CURRENT PRESENT
RELAY TEST BLOCKED
AMPS SIMULATION ON
SIMULATION
HAS BEEN ENABLED
CURRENT SIMULATION
HAS BEEN DISABLED
239 Motor Protection Relay
4 PROGRAMMING
or
key to scroll to the
VALUE
VALUE
4
4-39