4 PROGRAMMING
If the test is attempted while current is present, the setpoint will be forced to NORMAL MODE
and the following flash message will be displayed for 3 seconds.
If 6 7(67,1*? &855(17 6,08/$7,21?6,08/$7,21 is 21 , the setpoint will be forced to NORMAL
MODE and the following flash message will be displayed for 3 seconds.
If testing is attempted via the serial port while phase or ground current is present or simulation
mode is on, an error code will be returned.
While the 23(5$7,21 7(67 setpoint is displayed, use the
desired output relay and/or status indicator to be tested. As long as the test message remains
displayed the respective output relay and/or status indicator will be forced to remain energized.
As soon as a new message is selected, the respective output relay and/or status indicator return
to normal operation.
As a safeguard, relay and LED test will turn off automatically if:
•
power to the 239 is turned off and on
•
phase or ground current is detected by the 239
•
current simulation is turned on
•
new message is displayed
c) CURRENT SIMULATION
Simulated currents can be forced instead of the actual currents sensed by the external CTs con-
nected to the 239. This allows verification of all current related relay functions such as timed over-
load trip. It also allows verification that external trip and alarm wiring is responding correctly.
•
SIMULATION: Enter the required simulation phase and ground currents in the following mes-
sages. Enter ON to switch from actual currents to the programmed simulated values. This com-
mand will be ignored if real phase or ground current is present. Set this setpoint 2)) after
simulation is complete. As a safeguard, simulation will automatically turn off if:
•
real phase or ground current is detected while in simulation mode
•
power to the 239 is turned off and on
time programmed in the 6 7(67,1*?&855(17 6,08/$7,21?6,08/$7,21 (1$%/(' )25 setpoint
•
has elapsed since simulation was first enabled
•
239 is tripped
When current simulation is turned on the following flash message will be displayed for 3 seconds.
When current simulation is turned off the following flash message will be displayed for 3 seconds.
GE Multilin
Courtesy of NationalSwitchgear.com
RELAY TEST BLOCKED
CURRENT PRESENT
RELAY TEST BLOCKED
AMPS SIMULATION ON
SIMULATION
HAS BEEN ENABLED
CURRENT SIMULATION
HAS BEEN DISABLED
239 Motor Protection Relay
4 PROGRAMMING
or
key to scroll to the
VALUE
VALUE
4
4-39