GE 239 Instruction Manual page 15

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

1 OVERVIEW
FUSE TYPE/RATING
5 × 20mm, 2.5 A, 250V
Slow blow, High breaking capacity
ENVIRONMENT/GENERAL INFO
POLLUTION DEGREE: 2
OVERVOLTAGE CATEGORY: 2
INSULATION VOLTAGE: 300 V
OPERATING TEMPERATURE RANGE: 0°C to 60°C
STORAGE TEMPERATURE RANGE: –40°C to 70°C
IP CLASS:
40
INSTALLATION
WARNING:
HAZARD may result if the
product is not used for its
intended purpose.
VENTILATION REQUIREMENTS: None
CLEANING REQUIREMENTS: None
NOTE: Specifications subject to change without notice.
GE Multilin
Courtesy of NationalSwitchgear.com
TYPE TESTS
DIELECTRIC STRENGTH: 2.0 kV for 1 minute to
INSULATION RESISTANCE:IEC255-5, 500 V DC
TRANSIENTS:
IMPULSE TEST:
RFI:
EMI:
STATIC:
HUMIDITY:
TEMPERATURE:
ENVIRONMENT:
DUST/MOISTURE: NEMA 12/IP53
PACKAGING
SHIPPING BOX:
SHIP WEIGHT:
CERTIFICATION/COMPLIANCE
ISO:
UL:
CSA:
239 Motor Protection Relay
1 OVERVIEW
relays, CTs, power supply
ANSI C37.90.1 Oscillatory 2.5
kV / 1 MHz; ANSI C37.90.1 Fast
Rise 5 kV / 10 ns; Ontario Hydro
A-28M-82; IEC255-4 Impulse/
High Frequency Disturbance
Class III Level
IEC 255-5 0.5 Joule 5 kV
50 MHz/15 W Transmitter
C37.90.2 Electromagnetic Inter-
ference @ 150 MHz and 450
MHz, 10 V/m
IEC 801-2 Static Discharge
95% non-condensing
–10°C to +60°C ambient
IEC 68-2-38 Temp/Humidity
Cycle
8½" × 6" × 6" (L × H × D)
215 mm × 152 mm × 152 mm
(L × H × D)
5 lbs. / 2.3 kg
Manufactured under an
ISO9001 recognized program
Recognized under E83849
Approved under LR41286
1
1-9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents