4 PROGRAMMING
SETPOINT
]] SETPOINTS
]] S5 TESTING
MESSAGE
MESSAGE
] TEST CONFIGURATION
]
MESSAGE
MESSAGE
4
] TEST RELAYS & LEDS
]
MESSAGE
MESSAGE
] CURRENT SIMULATION
]
MESSAGE
MESSAGE
] ANALOG OUTPUT
] SIMULATION
MESSAGE
MESSAGE
4-36
Courtesy of NationalSwitchgear.com
SETPOINT
]] SETPOINTS
]] S1 239 SETUP
4
MESSAGE
DISABLE START
PROTECTION: NO
3
PROTECTION DISABLED
MESSAGE
FOR: 15 min
DISABLE STATISTICS
LOGGING: NO
4
MESSAGE
OPERATION TEST:
NORMAL MODE
3
MESSAGE
4
MESSAGE
SIMULATION: OFF
3
SIMULATION ENABLED
MESSAGE
FOR: 15 min
PHASE A CURRENT:
0 A
PHASE B CURRENT:
0 A
4
MESSAGE
SIMULATION: OFF
3
SIMULATION ENABLED
MESSAGE
FOR: 15 min
ANALOG OUTPUT FORCED
TO: OFF %
SEE NEXT PAGE
239 Motor Protection Relay
Range: NO, YES
Range: 5 to 300, UNLIMITED
Step: 5 min.
Range: NO, YES.
Range: NORMAL MODE, TRIP RELAY & LED
ON, ALARM RELAY & LED ON, AUXILIARY
RELAY & LED ON, SERVICE RELAY & LED
ON, ALL RELAYS ON, PICKUP LED ON,
COMMUNICATE LED ON, ALL LEDS ON
Range: ON, OFF
Range: 5 to 300, UNLIMITED
Step: 5 min.
Range: 0 to 10000, step 1 A (CT PRI SET > 50 A)
Range: Same as PHASE A CURRENT
Range: Same as PHASE A CURRENT
PHASE C CURRENT:
0 A
GROUND CURRENT:
0.0 A
Range: OFF, ON
Range: 5 to 300, UNLIMITED
Step: 5 min.
Range: 0.0 to 120.0, OFF
Step: 0.1 %
4 PROGRAMMING

4.9 S5: TESTING

0 to 1000 step 0.1 A (CT PRI SET ≤ 50 A)
Range: 0 to 10000, step 1 A
(CT PRI SET > 50 A)
0 to 1000 step 0.1 A
(CT PRI SET ≤ 50 A)
DESIGNATES SETPOINTS THAT
ARE ONLY VISIBLE IF ANALOG
OUTPUT OPTION IS INSTALLED