05: Execute Operation - GE 239 Instruction Manual

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

7 COMMUNICATIONS
Slave Response
SLAVE ADDRESS
FUNCTION CODE
BYTE COUNT
DATA 1
DATA 2
DATA 3
CRC
Modbus Implementation:Force Single Coil
239 Implementation:
This function code allows the master to request a 239 to perform specific command operations. The
command numbers listed in the Commands area of the memory map correspond to operation code
for function code 05.
The operation commands can also be initiated by writing to the Commands area of the memory map
using function code 16. Refer to Section 7.14: 16: PERFORMING COMMANDS on page 7–10 for
complete details.
a) MESSAGE FORMAT AND EXAMPLE
Reset 239 (operation code 1).
Master Transmission
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE
CODE VALUE
CRC
Slave Response
SLAVE ADDRESS
FUNCTION CODE
OPERATION CODE
CODE VALUE
CRC
GE Multilin
Courtesy of NationalSwitchgear.com
Bytes
- 1 byte
- 1 byte
- 1 byte
- 2 byte
- 2 bytes
- 2 bytes
- 2 bytes
Execute Operation
Bytes
- 1 byte
- 1 byte
- 2 bytes
- 2 bytes
- 2 bytes
Bytes
- 1 byte
- 1 byte
- 2 bytes
- 2 bytes
- 2 bytes
239 Motor Protection Relay
7 COMMUNICATIONS
Example (hex)
11
message from slave 11
03
read registers
06
3 registers = 6 bytes
00 00
bit set corresponding to command 13
00 00
value in address 006C
00 00
value in address 006D
EC B5
CRC calculated by slave

7.9 05: EXECUTE OPERATION

Example (hex)
11
message for slave 11
05
execute operation
00
reset command (operation code 1)
01
FF
perform function
00
DF
CRC calculated by the master
6A
Example (hex)
11
message from slave 11
05
execute operation
00
reset command (operation code 1)
01
FF
perform function
00
DF
CRC calculated by slave
6A