GE 239 Instruction Manual page 126

Multilin motor protection relay
Hide thumbs Also See for 239:
Table of Contents

Advertisement

7 COMMUNICATIONS
Table 7–1: 239 MEMORY MAP (Sheet 10 of 18)
REG
GROUP
ADDR
(HEX)
1055
1056
1057
1058
PHASE
S/C
1059
105A
105B
105C
105D
105E
105F
1060
IMMEDIATE
OVERLOAD
1061
1062
1063
1064
1065
1066
1067
1068
MECHANICAL
JAM
1069
106A
106B
7
106C
106D
106E
106F
1070
UNDER-
CURRENT
1071
1072
1073
1074
1075
1076
1077
1078
UNBALANCE
1, 2, 3,
,
,
,
, †, ‡
*
**
***
****
See page 7–30 for explanation of Table notes.
7-22
Courtesy of NationalSwitchgear.com
DESCRIPTION
Reserved
Reserved
Reserved
Phase S/C Trip
Phase S/C Pickup
Phase S/C Delay
Reserved
Reserved
Reserved
Reserved
Reserved
Immediate Overload Alarm
Immediate Overload Pickup
Inhibit On Start For
Reserved
Reserved
Reserved
Reserved
Reserved
Mechanical Jam Function
Mechanical Jam Pickup
Mechanical Jam Delay
Inhibit On Start For
Reserved
Reserved
Reserved
Reserved
Undercurrent Function
Undercurrent Pickup
Undercurrent Delay
Reserved
Reserved
Reserved
Reserved
Reserved
Phase Unbalance Trip
239 Motor Protection Relay
7 COMMUNICATIONS
REGISTER
STEP
UNITS &
VALUE
VALUE
SCALE
RANGE
0-3
1
---
10-110
1
0.1 xCT
0-60000
10
ms
0-1
1
---
5-110
1
0.1
xFLC
0-6001
1
s
0-4
1
---
1-100
1
0.1
xFLC
0-250
1
s
0-6001
1
s
0-5
1
---
5-100
1
0.01xF
LC
0-250
1
s
0-1
1
---
FOR-
FACTORY
MAT
DEFAULT VALUE
(CONVERTED)
F19
0 = OFF
F1
100 = 10.0 xCT
F1
0 ms
F20
0 = OFF
F1
10 = 1.0 xFLC
3
F1
6001 = UNLIMITED
F23
0 = OFF
F1
2.0 x FLC
F1
2 s
3
F1
6001 = UNLIMITED
F21
0 = OFF
F1
0.50 xFLC
F1
2 s
F20
1 = ON
GE Multilin