54
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
13857
Message buffer full. The value of the Message Length parameter may be too
small.
13858
Message filling error. The value of the Message Length parameter may be too
small.
13863
Device suspended. The reason could be that the link is not properly established
(for example, incorrect communication cable wiring) or the client station does
not respond.
13864
Message sending error. The error may be the result of a problem in communic-
ation cable wiring or hardware.
13865
Remote device replies with no acknowledged response. The client did not accept
the message but responded with a negative acknowledgment instead. Not used
in the unbalanced mode.
13866
Link not ready. A message is sent to a link with a non-established communication.
13870
Confirmation timeout. An activation confirmation to a command was not received
from the IEC client in the time defined by the Reply Timeout parameter.
13871
Negative confirmation received. The activation confirmation received from the
IEC client was negative, that is, the command failed.
13872
Device taken out of use.
13881
Device taken in use.
17600
Remote link continuously busy. The Data Flow Control (DFC) bit of the messages
from the client is set for more than 15 s.
17601
Timeout while transmitting. The CTS signal or the end of transmitted message
is not received in correct time. The DE attribute controls the CTS waiting time;
the transmission time of the message is automatically calculated.
17602
Timeout while waiting for an acknowledgment to a message.
17604
Link not ready. The application level sends a command before the communication
between the server and the client is established.
17605
Remote link busy.
17606
Remote link not responding. The server does not receive a reply from the client.
17607
Channel set in use.
17608
Channel set out of use.
17610
Receiver out of buffers.
17611
Dial-up function inactivated.
17612
Dial-up function activated.