Technical Reference; About This Section; Iec 61850 Data Modeling; General Information About Iec 61850 Data Modeling - ABB COM600 series User Manual

Substation management unit
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

5.
5.1.
5.2.
5.2.1.
5.2.2.
5.2.2.1.
Name
Type
stVal
BOOLEAN
q
Quality
t
TimeStamp
44
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual

Technical reference

About this section

This section provides reference information about the following issues:

IEC 61850 data modeling

Attributes
Status codes
IEC 61850 data modeling

General information about IEC 61850 data modeling

The relationship between the IEC 61850 data modeling and IEC103 OPC Server is
described in this section.
For each data class, there is a table giving a detailed description about the relation between
the IEC103 data and IEC 61850 data object attributes and services. The tables also
describe how the data is presented on the OPC Server name space.
The columns in the tables have the following content types:
Name specifies the OPC item name of the attribute/service.
Type specifies the IEC 61850 type of the attribute.
Value/ Value range specifies the allowed values and ranges of the attribute/service.
Mandatory/Optional specifies whether the attribute is considered as mandatory or
optional according to the IEC 61850 standard.
OPC data types specify the OPC data type used for the OPC item.

Data objects for status information

Single point status (SPS)

SPS represents ASDUs 1 and 2.
Table 5.2.2.1-1 Single point status (SPS) information
Value/ Value
range
TRUE | FALSE
Mandatory
Protocol informa-
/Optional
tion element
M
DPI (1: OFF, 2:
ON)
M
Time Validity
M
CP32
1MRS752278
OPC data types
VT_BOOL
VT_I4
VT_DATE