ABB COM600 series User Manual page 33

Substation management unit
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS752278
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
Common Data
WYE
Class
Phase A
Addresses
Phase A Function
0...255
Type
Default: 160
Phase A Index
1...255
Default: 1
Phase A Information
0...255
Number
Default: 144
Phase B
Addresses
Phase B Function
0...255
Type
Default: 160
Phase B Index
1...255
Default: 2
Phase B Information
0...255
Number
Default: 144
Phase C
Addresses
Phase C Function
0...255
Type
Default: 160
Phase C Index
1...255
Default: 3
Phase C Information
0...255
Number
Default: 144
Neutral Addresses
Neutral Function
0...255
Type
Default: 160
Neutral Index
1...255
Default: 4
Neutral Information
0...255
Number
Default: 144
Description
Common data class according to IEC
61850
IEC103 function type for phase A
IEC103 index for phase A
IEC103 information number for phase A
IEC103 function type for phase B
IEC103 index for phase B
IEC103 information number for phase B
IEC103 function type for phase C
IEC103 index for phase C
IEC103 information number for phase C
IEC103 function type for neutral
IEC103 index for neutral
IEC103 information number for neutral
33