ABB COM600 series User Manual page 38

Substation management unit
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

38
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Common Data
BSC
Class
Subtype of the
current data
object: Same com-
mand and indica-
tion addresses
Addresses
Command ASDU
0...255
Type
Default: 20
Command Function
0...255
Type
Default: 101
Command Informa-
0...255
tion Number
Default: 105
Scale and Unit
Scale
Default: None
Subtype of the
current data
object: Separate
command and
indication
addresses
Addresses
Command ASDU
0...255
Type
Default: 20
Command Function
0...255
Type
Default: 101
Command Informa-
0...255
tion Number
Default: 105
Indication Function
0...255
Type
Default: 101
Indication Index
1...255
Default: 1
Indication Informa-
0...255
tion Number
Default: 105
Scale and Unit
Description
Common data class according to IEC
61850
IEC103 command ASDU type
IEC103 command function type
IEC103 command information number
Scale to be used with this data object
IEC103 command ASDU type
IEC103 command function type
IEC103 command information number
IEC103 indication function type
IEC103 indication index
IEC103 indication information number
1MRS752278