Table 17. Environmental and safety standards (continued)
EMC (Immunity)
Agency markings
Operating temperature
Storage temperature
Transit temperature
Relative humidity
Operating altitude
Transit altitude
Audible noise
Table 18. Battery
Rating
Fuse
Type
Monitoring
Battery port
EBM battery cable length
66
6U Rack or Tower UPS RT8.0kVA and RT11.0VA and Maintenance Bypass Installation and User's Guide
IEC 61000-3-2 (-3-12)
IEC 61000-3-3 (-3-11)
IEC 61000-2-2
IEC 61000-4-2, Level 3
IEC 61000-4-3, Level 3
IEC 61000-4-4, Level 4 (also on signal ports)
IEC 61000-4-5, Level 4, Criteria B
IEC 61000-4-6, Level 3
IEC 61000-4-8, Level 4
IEC 61000-4-11
CE / C-Tick
0 to 40°C (32 to 104°F) in Online mode, with linear derating for altitude
Note: Thermal protection switches load to Bypass in case of overheating.
0 to 40°C (32 to 104°F) with batteries
-15 to 60°C (5 to 140°F) without batteries
-25 to 55°C (-13 to 130°F)
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Up to 10,000 meters (32,808 ft) above sea level
< 48 dBA at 1 meter typical for 6-8kVA models
< 50 dBA at 1 meter typical for 11kVA model
EBMs
240Vdc 20 x 12V, 9Ah
80A
Sealed, maintenance-free, valve-regulated, lead-acid, with minimum
3-year float service life at 25°C (77°F).
Lifetime is reduced above 30°C (86°F).
Advanced monitoring for earlier failure detection and warning
External three-pole SBS75G White connector on Power Module for
connecting to EBM
40cm (15.7in)

Advertisement