Lenovo RT8.0kVA Installation And User Manual page 23

6u rack or tower ups rt8.0kva and rt11.0va
Hide thumbs Also See for RT8.0kVA:
Table of Contents

Advertisement

On/Off settings
Submenu
High Efficiency mode
Bypass transfer
Interrupt time
Overload prealarm
Redundancy mode
Cold start
Forced reboot
Auto restart
Auto start
Available settings
[Enabled] [Disabled]
Power the output from
Bypass for high efficiency
[Transfer if BP AC NOK]
[Enabled] [Disabled]
Allow transfer on Bypass
out of tolerance
If Bypass transfer is
enabled, Interrupt time:
[10ms] [20ms]
Define break duration when
transfer on Bypass
[10%] ... [102%]
Load % when overload
alarm occurs
[Unitary UPS] [Hot Standby]
Force slew rate value to
0.5Hz/s
[Enabled] [Disabled]
Authorize the product to
start on battery power.
[Enabled] [Disabled]
If utility power recovers
during a shutdown
sequence:
If Enabled, the shutdown
sequence will complete
and wait 10 seconds prior
to restart. If Disabled, the
shutdown sequence will
not complete and restart
will occur immediately.
[Enabled] [Disabled]
Authorize the product to
restart automatically when
utility power recovers
after a complete battery
discharge.
[Enabled] [Disabled]
The UPS automatically
starts up as soon as utility
power is available (no need
to press the
button).
Default settings
[Disabled]
[Enabled] for 8PX and 9PX
models
[Disabled] for 8KX and 9KX
models
[10ms]
[102%]
[Unitary UPS]
[Enabled]
[Enabled]
[Enabled]
[Disabled]
.
Chapter 2
Presentation
11