Table 13. AC input and output (1Phase models) (continued)
Table 14. AC input and output (3Phase models)
AC Input power
AC Output power
Table 15. Weights and dimensions (Power Module)
Model (Power Module)
8K Power Module (PX)
8K Power Module (KX)
11K Power Module (PX)
11K Power Module (KX)
Minimum rack depth for UPS with MBP: 900mm (35.4 inches)
Table 16. Weights and dimensions (EBM)
Model (EBM)
5594-9BX
Table 17. Environmental and safety standards
EMC certifications
EMC (Emissions) - for output cable <
10m
5594-8KX
230VAC, 8000VA, 7200W, 34.8A;
240VAC, 8000VA, 7200W, 33.3A;
250VAC, 8000VA, 7200W, 32.0A
5594-8PX
350/360/380/400/415/430VAC,
50/60Hz, 3ph, 13.3A
50/60Hz, 1ph;
200VAC, 8000VA, 7200W, 40.0A;
208VAC, 8000VA, 7200W, 38.5A;
220VAC, 8000VA, 7200W, 36.4A;
230VAC, 8000VA, 7200W, 34.8A;
240VAC, 8000VA, 7200W, 33.3A;
250VAC, 8000VA, 7200W, 32.0A
Dimensions D x W x H (mm / inch)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
700 x 440 x 130 (27.6 x 17.3 x 5.1)
Dimensions D x W x H (mm / inch)
680 x 440 x 130 (26.8 x 17.3 x 5.1)
IEC/EN 62040-1: 2008
IEC/EN 62040-2: 2006 Cat. C2
IEC/EN 62040-3: 2011
IEC 60950-1
CISPR22 Class A
AS/NZS 22 Class A
5594-9KX
230VAC, 11000VA, 10000W, 47.8A;
240VAC, 11000VA, 10000W, 45.8A;
250VAC, 10000VA, 9000W, 40.0A
5594-9PX
350/360/380/400/415/430VAC,
50/60Hz, 3ph, 16.7A
50/60Hz, 1ph;
200VAC, 10000VA, 9000W, 50.0A;
208VAC, 10000VA, 9000W, 48.1A;
220VAC, 11000VA, 9900W, 50.0A;
230VAC, 11000VA, 10000W, 47.8A;
240VAC, 11000VA, 10000W, 45.8A;
250VAC, 10000VA, 9000W, 40.0A
Weight (lb / kg)
51 / 23
42 / 19
51 / 23
46 / 21
Weight (lb / kg)
143 / 65
Appendix A. Specifications