DC Analog Inputs

All DC Analog Card options are available with 16 inputs.
DC Analog
Inputs
The inputs may be voltage or current.
With the exception of the 517-0478 and 517-0479 cards that use adapter
modules, there are no on-board option jumpers; each option requires a different
card.
All inputs should have shield connected at source of signal. Shields can
!
alternately be connected to the auxiliary ground on D25 power supply
terminal block. DO NOT ground at both ends of cable.
Shielding
Table of typical digital counts stored in the D25 System Point Database
Table: Digital
Counts
representing inputs at several input levels, and scaling settings, for each DC
Analog board option:
± 5V
± 1 mA
± 5 mA
± 10 mA
± 20 mA
@ 83.333% Scaling
@ 100% Scaling
@ 200% Scaling
GE Information
10%
25%
50%
.5V
1.25V
2.5V
.1 mA
.25 mA
.5 mA
.5 mA
1.25 mA
2.5 mA
1 mA
2.5 mA
5 mA
2 mA
4 mA
10 mA
2731
6826
13653
3277
8192
16383
6553
16383
32767
994-0081-3.00-21
User's Manual
75%
Nom
120%
3.75V
5V
.75 mA
1 mA
1.2 mA
3.75 mA
5 mA
6 mA
7.5 mA
10 mA
12 mA
15 mA
20 mA
24 mA
20479
27306
32767
24575
32767
>32767
>32767
>32767
>32767
D25
6V
65